5895XL Manual - P/N 151142-L8:L 08/09/2017 13
Calculating Current Draw and Standby Battery Before You Begin Installing
SD500-ANM Aux. Pwr Standby: 8 mA mA
Alarm: 60 mA mA
SLC Standby/Alarm: .55 mA mA mA
SD500-SDM SLC Standby/Alarm: .55 mA mA
Aux. Pwr Standby: 20 mA mA
Alarm: 106 mA mA
SLC Accessory Bases
SD505-6RB Standby/Alarm: .082 mA mA mA
SD505-6SB Aux. Pwr Standby: 1 mA mA
Alarm: 32 mA mA
SLC Standby/Alarm .082 mA mA mA
SD505-DUCTR Aux. Pwr Standby: 20 mA
2
mA
Alarm: 62 mA
2
mA
SLC Standby/Alarm: .5 mA mA mA
SD505-DTS-K None, included with SD505-DUCTR worst case.
SD505-DUCT None, included with detector current.
SLC Isolator Devices
SD500-LIM (100 max/loop) Standby/Alarm .092 mA mA mA
SD505-6IB
Accessories Modules
5815XL SLC Loop Expander (63 max.) Standby/Alarm: 55 mA mA mA
6860 Remote LCD Annunciator. (16 max.) Standby: 25 mA mA
Alarm: 50 mA mA
5860 Remote LCD Annunciator. Standby: 20 mA mA
Alarm: 25 mA mA
6855 Remote LCD Annunciator Standby: 20 mA mA
Alarm: 25 mA mA
5824 Serial/Parallel Printer Interface (4 max.) Standby/Alarm: 45 mA mA mA
5895XL Power Supply (16 max.) Standby/Alarm: 10 mA mA mA
5496 NAC Expander Standby/Alarm: 10 mA mA mA
5865-4 LED Annunciator Module
(with reset and silence switches)
(8 max.) Standby: 35 mA mA
Alarm: 145 mA mA
5865-3 LED Annunciator Module Standby: 35 mA mA
Alarm: 145 mA mA
5880 LED I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
5883 Relay Interface (32 max.) Standby: 0 mA mA
Alarm: 220 mA
(22 mA per relay)
mA
EVS-50W or EVS-125W Audio Amplifier
with/without EVS-CE4
(4 max.) Standby: 10 mA mA
Alarm: 10 mA mA
EVS-INT50W Internal Amplifier (4 max.) Standby: 52 mA mA
Alarm @ 25V: 275 mA mA
Alarm @ 70V: 310 mA
mA
EVS-VCM Voice Control Module (1max.) Standby: 70 mA mA
Alarm: 100 mA mA
EVS-SW24 Switch Expander (5 max.) Standby: 10 mA mA
Alarm: 25 mA mA
Table 2.5 Current Draw Worksheet for SD SLC Devices
Device # of Devices Current per Device
Standby
Current
Alarm
Current