24 5895XL Manual - P/N 151142-L8:L 08/09/2017
Hardware Installation Flexputs™ I/O Circuits
2. Configure the circuit for Class A in programming.
Figure 3.13 Class A Notification Appliance Circuit Configuration
3.5.3 Conventional Initiation Circuits
This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configura-
tions.
Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL
panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 3.14.
2. Configure the circuit through programming (see FACP Installation Manual).
Figure 3.14 Class B Input Switches
Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL
panel.
Regulated
NOTE: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
Figure 3.13 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
UL Listed EOL
4.7 k