5895XL Manual - P/N 151142-L8:L 08/09/2017 23
Flexputs™ I/O Circuits Hardware Installation
3.5.2 Releasing Operations
Approved releasing solenoids are list in Table 3.8. Do not mix cross alarming zones with smoke verification zones. There must be at
least two automatic detection devices in each protected space. Spacing must be reduced to 0.7 times the linear spacing in accordance
with NFPA 72.
Class B Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A.
To install a Class B notification appliance circuit:
1. Wire Class B Notification appliances as shown in Figure 3.12.
2. Configure the circuit through programming.
Figure 3.12 Class B Notification Appliance Circuit Wiring
Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 3.13.
Table 3.8 Approved Releasing Solenoids
Manufacturer Part Number Rating Current Freq
Asco T8210A107 24 VDC 3A max 0 Hz
8210G207 24 VDC 3A max 0 Hz
alarm polarity shown.
UL Listed EOL
4.7 k
Supervised
Power Limited
Notification Wiring