5895XL Manual - P/N 151142-L8:L 08/09/2017 25
Flexputs™ I/O Circuits Hardware Installation
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 3.15.
2. Configure the circuit through programming.
Figure 3.15 Class A initiating Switches
3.5.4 Installing 2-Wire Smoke Detectors
Any compatible U.L. listed two-wire smoke detector can be used with the 5895XL panel (see Appendix A for list of compatible smoke
detectors). Figure 3.16 and Figure 3.17 illustrate how to connect a UL listed 2-wire detector to the control panel.
Class B Installation
To install a Class B two-wire smoke detector, wire as shown in Figure 3.16.
Figure 3.16 Two-Wire Class B Smoke Detector
NOTE: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
Figure 3.15 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
Note:
I/O circuit 5
used as an example.
Any I/O circuit
could be used.
UL Listed EOL
4.7 k