Model RPS-1000 Installation Manual 151153
2-3
* Regulated/special application when used for releasing.
Table 2-1: Terminal Strip Description and Electrical Ratings
Terminal # and Label
Description
Rating
Voltage Current
1 L AC input (hot) 120/240 VAC,
50/60 Hz
2.7 A
1.4 A
2 G Earth ground N/A N/A
3 N AC input (neutral) 120/240 VAC,
50/60 Hz
2.7 A
1.4 A
4 X I/O 6* Flexput™ Circuit 24 VDC 3.0 A Notification Circuits
5 O 100 mA Initiation Circuits
6 X I/O 5* Flexput™ Circuit 24 VDC 3.0 A Notification Circuits
7 O 100 mA Initiation Circuits
8 X I/O 4* Flexput™ Circuit 24 VDC 3.0 A Notification Circuits
9 O 100 mA
Initiation Circuits
10 X I/O 3* Flexput™ Circuit 24 VDC 3.0 A Notification Circuits
11 O 100 mA Initiation Circuits
12 X I/O 2* Flexput™ Circuit 24 VDC 3.0 A Notification Circuits
13 O 100 mA Initiation Circuits
14 X I/O 1* Flexput™ Circuit 24 VDC 3.0 A Notification Circuits
15 O 100 mA Initiation Circuits
16 B SBUS OUT SBUS communication 5 VDC 100 mA
17 A
18 + SBUS power 24 VDC 1.0 A
19 -
20 B SBUS IN Used for Class A installations
21 A
22 +
23 -
24 N.C. RELAY 2 General Purpose Relay 2 24 VDC 2.5 A
25 C
26 N.O.
27 N.C. RELAY 1 General Purpose Relay 1 24 VDC 2.5 A
28 C
29 N.O.
30 B SBUS IN/
OUT
RPS-1000 communication with
main panel or to controlling
RPS-1000 if daisy-chained
5 VDC 100 mA
31 A
32 + MAIN RPS-1000 SBUS power (from
IFP-1000 or IFP-1000ECS)
24 VDC 10 mA
33 -