EasyManua.ls Logo

Honeywell SILENT KNIGHT Farenhyt Series - Installing 4-Wire Smoke Detectors

Honeywell SILENT KNIGHT Farenhyt Series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model RPS-1000 Installation Manual 151153
3-11
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-13 uses both I/O circuit 5 and 6, so in programming
it would be referred to as point 5.
3.5.5 Installing 4-Wire Smoke Detectors
Any compatible U.L. listed four-wire smoke detector can be used with the RPS-1000
panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure
3-13 illustrate how to connect a UL listed four-wire detector to the control panel.
Installing a Class B 4-Wire Smoke Detector
Figure 3-14 illustrates how to install a 4-wire Class B smoke detector.
Conventions used for wiring 4-wire Class B loops:
1. Up to three Class B 4-wire smoke detector loops can be connected to the control panel at
once.
2. Each Class B loop input is paired with a unique power source as shown in Figure 3-14.
3. Each loop gets smoke power from the even numbered I/O circuit and the contact input is
connected to the odd numbered I/O circuit.
Figure 3-14 Class B 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-14 uses both I/O circuit 5 and 6, so in programming
it would be referred to as point 5.
Air Products
PAM-2
Model 160150
Supervision
Module
UL Listed
EOL Resistor
Model 7628
ESL 449CT
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.

Related product manuals