Model RPS-1000 Installation Manual 151153
3-7
spacing in accordance with NFPA 72.
3.5.2.1 Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A.
To install a Class B notification appliance circuit:
1. Wire Class B Notification appliances as shown in Figure 3-8.
2. Configure the circuit through programming.
Figure 3-8 Class B Notification Appliance Circuit Wiring
3.5.2.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at
the back of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 3-9.
Table 3-1: Approved Releasing Solenoids
Manufacturer Part Number Rating Current Freq
Asco T8210A107 24 VDC 3A max 0 Hz
8210G207 24 VDC 3A max 0 Hz
Alarm
Polarity
UL Listed EOL
Model 7628
4.7 k
Supervised
Power Limited
Notification Wiring
Regulated