Hardware Installation 151153
3-10
3.5.4 Installing 2-Wire Smoke Detectors
Any compatible U.L. listed two-wire smoke detector can be used with the RPS-1000
panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure
3-13 illustrate how to connect a UL listed 2-wire detector to the control panel.
Class B Installation
To install a Class B two-wire smoke detector, wire as shown in Figure 3-12.
Figure 3-12 Two-Wire Class B Smoke Detector
2-Wire Class A Smoke Detector Installation
To install a Class A two-wire smoke detector, wire as shown in Figure 3-13.
Figure 3-13 Two-Wire Class A Smoke Detector Connections
Note:
I/O circuit 5
used as an example.
Any I/O circuit
could be used.
UL Listed EOL
Model 7628
4.7 k
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.