EasyManua.ls Logo

Honeywell SILENT KNIGHT Farenhyt Series - Current Draw Worksheet

Honeywell SILENT KNIGHT Farenhyt Series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Before You Begin Installing 151153
2-6
2.6.2 Current Draw Worksheet
For each RPS-1000* in the installation, use this worksheet to determine current
requirements during alarm/battery standby operation. (Copy this page if additional
space is required.)
*Use a separate worksheet for each RPS-1000.
Table 2-4: Current Draw Calculations
Device
Number of
Devices
Current per Device
Standby
Current
Alarm Current
For each device use this formula: This column X This column = Current per number of
devices.
RPS-1000 Intelligent Power Module
(Current draw from battery)
1* Standby: 40 mA 40 mA
Alarm: 160 mA 160 mA
Additional RPS-1000
(Daisy-chained to this module)
(7 max.) Standby: 10 mA
Alarm: 10 mA
Addressable Devices (381 max.) Standby: 0.55 mA
Alarm: 0.55 mA
5815XL SLC Expander (2 max.) Standby: 55 mA mA
Alarm: 55 mA mA
RA-1000 or RA-100 Remote Fire
Alarm Annunciator
(8 max.) Standby: 20 mA mA
Alarm: 25 mA mA
5824 Serial / Parallel Module (2 max.) Standby: 45 mA mA
Alarm: 45 mA mA
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.) Standby: 35 mA mA
Alarm: 145 mA mA
5865-3 LED Annunciator Standby: 35 mA mA
Alarm: 145 mA mA
5880 Generic LED Driver Module Standby: 35 mA mA
Alarm: 200 mA mA
A Total System Current
**Auxiliary Devices Refer to devices manual for current rating.
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Current
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA mA
Alarm: mA
mA
C Notification Appliances Current
mA
D Total current ratings of all devices in system (line A + line B + C) mA mA
E Total current ratings converted to amperes (line D x .001): A A
F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H
G Multiply lines E and F. Total standby AH AH
H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H
I Multiply lines E and H. Total alarm AH
AH
J ***Add lines G and I. Total ampere hours required AH

Related product manuals