Model RPS-1000 Installation Manual 151153
3-9
2. Configure the circuit through programming (see Section 7.5 of the IFP-1000 Installation
manual PN 151139 or IFP-1000ECS Installation manual PN 151460).
Figure 3-10 Class B Input Switches
3.5.3.2 Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull
stations, directly to the I/O circuits of the RPS-1000 panel.
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 3-11.
2. Configure the circuit through programming (see Section 7.5 of the IFP-1000 Installation
Manual PN 151139 or IFP-1000ECS Installation manual PN 151460).
Figure 3-11 Class A initiating Switches
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-11 uses both I/O circuit 5 and 6, so in programming
it would be referred to as point 5.
UL Listed EOL
Model 7628
4.7 k
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.