34-SM-03-01
Page 22
A
vailabilit
y
SMX1XX 10 25 70
TABLE III - OPTIONS (continued) Selection
Approval
Body Approval Type Location or Classification
None
Explosion Proof Class I, Div. 1, Groups A,B,C,D
Dust Ignition Proof Class II, Div. 1, Groups E,F,G
Suitable for use in Class III, Div. 1
Non-Incendive Class I, Div. 2, Groups A,B,C,D 1C
Factory Intrinsically Safe Class I, II, III, Div. 1, Groups
Mutual A,B,C,D,E,F,G
- -
T4 at Ta < 93
o
C
Explosion Proof Class I, Div. 1, Groups B,C,D
Dust Ignition Proof Class II, Div. 1 Groups E,F,G
Suitable for use in Class III, Div. 1
Non-Incendive Class I, Div. 2, Groups A,B,C,D 1J
Intrinsically Safe Class I, II, III, Div. 1, Groups
A,B,C,D,E,F,G
- -
T4 at Ta < 93
o
C
Explosion Proof Class I, Div. 1, Groups B,C,D
b
CSA Dust Ignition Proof Class II, III, Div. 1, Groups E,F,G 2J
Suitable for use in Class I, II, III, Div. 2, Groups
A,B,C,D,E,F,G
Intrinsically Safe Class I, II, III, Div. 1, Groups
A,B,C,D,E,F,G
- -
T4 at Ta < 93
o
C
Intrinsically Safe Ex II 1G EEx ia IIC T5
3S
Zone 0/1
Flameproof, zone 1 Ex II 2G EEx d IIC T6,
3D
Enclosure IP 66/67
Non-Sparking Ex II 3G EEx nA, IIC T6 3N
ATEX*
Zone 2 Vmax = 42 Vdc
T4 at Ta = 93
0
C
T5 at Ta = 80
0
C
T6 at Ta = 65
0
C
(Honeywell). Enclosure IP 66/67
Multiple Marking**
Ex II 1 G EEx ia IIC T4, T5, T6
Int. Safe, Zone 0/1, or
Ex II 2 G EEx d IIC T5, T6 3H
Flameproof, Zone 1, or Ex II 3 G EEx nA, IIC T6 (Honeywell)
Non-Sparking, Zone 2
Enclosure IP 66/67
*See ATEX installation requirements in the ST 3000 User's Manual
None 9X
The
user
must
determine
the
type
of
protection
required
for
installation
of
the
equipment
.
The user shall then check the box [D] adjacent to the type of protection used on the
equipment certification nameplate. Once a type of protection has been checked on the
nameplate, the equipment shall not then be reinstalled using any of the other certification
types.
TABLE IV
Factory Identification XXXX
RESTRICTIONS
Restriction Available Only With Not Available With
Letter Table Selection Table Selection
III
b
Select only one option from this group.
c
I
_ _ H
h
III
EU
j
I
_ 2 _
n
III 1C, 1J, 2J
o
III CR, S4 or B5
p
III Functions in the analog mode only.
t
III S2, T2 or V2
u
III 1C, 1J, 2J
2
III FB
Example: SMA125-E1A-00000-MB,MC,1C + XXXX
a
3D or 3H