What does 'Tamper Alarm' mean on Honeywell Transmitter and how to solve it?
J
Jennifer RussellSep 13, 2025
This status on your Honeywell Transmitter indicates that the device is in Write Protect Mode and Tamper Mode is enabled, or Tamper Alarm alone is enabled, and outside attempts to change device configuration exceeded the set Tamper limit. Identify the source of tampering. If configuration changes are required, contact a qualified individual to unlock the Write Protection Mode feature, disable the Tamper Mode, and make the necessary updates.
D
Donna MartinAug 25, 2025
What to do if a critical failure has been detected on the HART, DE, or FF Electronics Module of Honeywell ST 700 Transmitter?
C
carla49Aug 25, 2025
If a critical failure is detected on the HART, DE, or FF Electronics Module, cycle power to the transmitter. If the problem continues, replace the Electronics Module.
E
ericvaldezAug 25, 2025
What to do if a critical failure has been detected in the Meter body of Honeywell ST 700?
J
Jacob AllenAug 26, 2025
If a critical failure has been detected in the Meter body, cycle power to the Transmitter. If the problem continues to occur, replace the Meter body.
M
meyerleonardAug 26, 2025
What to do if my Honeywell ST 700 displays 'Sensor Comm Timeout'?
R
Ricky LandryAug 26, 2025
If your Honeywell Transmitter shows a 'Sensor Comm Timeout' error, it means there's likely no response from the sensor. First, try replacing the Electronics module. If the issue continues, then replace the Meter Body.
J
Juan PerezAug 27, 2025
What does 'Electronic Module DAC Failure' mean on my Honeywell ST 700 Transmitter, and how do I fix it?
R
rochadonaldAug 27, 2025
An 'Electronic Module DAC Failure' on your Honeywell Transmitter indicates a failure in the Electronics Module, possibly due to the board temperature exceeding 140C, under-current or over-current status, packet error, SPI fault, or control word write fault. Begin by verifying that the environment temperature is within specified limits. Then, reset the device. If the problem persists, replace the Electronics Module.
J
Julie GarzaSep 9, 2025
What does 'URV Set Err. Span Config Button' mean on Honeywell ST 700 Transmitter and how to solve it?
J
Joseph MackSep 10, 2025
This status on your Honeywell Transmitter indicates that SET URV operation using external Span button was rejected. Verify the inputs are valid for the intended operation.
E
emmadavenportSep 7, 2025
What does 'RAM fault' mean on Honeywell Transmitter and how to solve it?
R
Robert GarzaSep 8, 2025
This status on your Honeywell Transmitter indicates that the RAM in the Sensor board is corrupt or the RAM database in the Sensor board is compromised. Reset the device. If the problem persists, replace the Meter Body.
S
savannah14Sep 8, 2025
What does 'NVM fault' mean on Honeywell Transmitter and how to solve it?
R
roberta91Sep 9, 2025
This status on your Honeywell Transmitter indicates that the NVM in the Sensor board is corrupt or the NVM in the Electronics module is corrupt. Reset the device. If the problem persists, replace the Meter Body.
K
Kevin MartinezSep 2, 2025
What does it mean when my Honeywell Transmitter is in 'Fixed Current Mode', and how do I change it?
A
Ann HenrySep 2, 2025
If your Honeywell Transmitter is in 'Fixed Current Mode,' it means the output current is fixed and not varying with the applied input. This can happen if the loop current mode is disabled or if loop test is active. Enable the Loop Current Mode if it is disabled, or exit the Loop Test mode if it is active.
V
Victoria CurtisAug 31, 2025
What causes 'Meter Body NVM Corrupt' on a Honeywell Transmitter, and how can I fix it?
M
Marilyn GarciaAug 31, 2025
If your Honeywell Transmitter displays 'Meter Body NVM Corrupt', it means the Meter Body NVM data has been corrupted. Try resetting the device. If the problem continues, replace the Meter Body.