Honeywell Process Solutions
ST 700 SmartLine Series HART/DE
Option
User’s Manual
34-ST-25-47
Revision 4.0
December 2016

Table of Contents

Questions and Answers:

Honeywell ST 700 Specifications

General IconGeneral
ManufacturerHoneywell
CategoryTransmitter
Communication ProtocolHART
Output4-20 mA
Ambient Temperature-40 to 85°C
Housing MaterialStainless Steel
Pressure RangeNot applicable (Temperature Transmitter)
Process ConnectionNot applicable (Temperature Transmitter)
Material316 SS
Storage Temperature-40 to 85°C
Protection RatingIP67

Summary

ST 700 Transmitter Series

Overview

Introduction to the ST 700 transmitter family, covering standard and basic models.

Introduction to the ST 700 Standard Transmitter

Features and Options

Lists protocols, HMI, materials, approvals, and mounting brackets for the ST 700.

Physical Characteristics

Describes the major assemblies: Electronics Housing and Meter Body.

Functional Characteristics

Explains the transmitter's function, output signals, and communication protocols.

ST 700 Standard Transmitter Nameplate

Details the information found on the transmitter's model nameplate.

Safety Certification Information

Locates and describes the approvals name plate for compliance information.

Transmitter Adjustments

Explains how to make zero and span adjustments using assemblies or tools.

Display Options – Standard Display

Details the characteristics of the Basic and Standard displays.

Optional 3-Button Assembly (Basic Display)

Lists features and benefits of the 3-button assembly for basic display.

Optional Integrated Two-Button Assembly (Standard Display)

Lists features and capabilities of the 2-button assembly for standard display.

Communication Model for ST 700 Standard Transmitter

Overview

Explains configuration for DE, HART, and Fieldbus protocols.

Digitally Enhanced (DE) Mode Communication

Details DE mode operation, its characteristics, and advantages.

HART Mode Communication

Explains HART protocol modes (point-to-point, multi-drop) and features.

Configuration Tools and Interfaces for ST 700 Standard Transmitter

Overview

Introduces tools for configuring HART or DE communication.

Pre-requisites

Assumes user knowledge of MC Toolkit/MCT404/202 and transmitters.

Application Design, Installation, Startup, and Operation

Refers to another manual for design, installation, and startup details.

MC Toolkit Participation

Explains prerequisites and potential consequences of using MC Toolkit.

MC Toolkit Software Applications

Describes FDC and MC Toolkit applications for transmitter configuration.

Configuration Databases

Explains the use of MC Toolkit for parameters in a transmitter database.

Configuration

Details online and offline configuration methods and considerations.

MC Toolkit–Transmitter Electrical/Signal Connections

Shows how to connect the MC Toolkit to HART or DE transmitters.

DE Transmitter Configuration for ST 700 Standard Transmitter

Configuration Personnel Requirements

Assumes use of MC Toolkit and lists other supporting tools.

MC Toolkit Software Application Overview

Explains MC Toolkit's online and offline configuration capabilities.

DE Transmitter Online Configuration

Outlines establishing communication and uploading configuration.

Uploading a Transmitter Configuration

Step-by-step guide to upload configuration from a DE transmitter.

Device Information Configuration

Details configuring Tag ID, Type, Firmware Version, etc.

General Configuration Parameters

Covers PV Type, Communication Mode, and FS Direction settings.

DE-Specific Configuration Parameters

Explains LRL, URL, LRV, URV, PV Units, Damping, and Conformity settings.

Transmitter Display Configuration

Covers configuring display units, custom tags, and flow values.

Monitor Status Configuration

Explains how to view input, output, SV, and communication status.

Saving the Configuration to File

Describes saving transmitter configuration to a file.

DE Transmitter Offline Configuration

Summarizes features and processes for offline DE configuration.

DE Offline File Management

Explains managing offline configuration files and templates.

Downloading in DE Offline Mode

Describes downloading offline configurations to a connected transmitter.

HART Transmitter Configuration for ST 700 Standard Transmitter

Overview

Introduces HART configuration using FDC for online and offline tasks.

Personnel Requirements

Assumes user familiarity with MC Toolkit and HART tools.

Overview of FDC Homepage

Explains the FDC homepage links for configuration options.

Settings

Customizing FDC for device detection, DD selection, and application settings.

Device Identification

Options for FDC to identify a device using Poll Address or Device TAG.

DD selection

Configuring FDC to select DD files based on device revision or generic files.

Manage DDs

Managing DD files: viewing, adding, or deleting them.

Add a DD file

Steps to add a DD file to FDC for a device.

Delete a DD file

Steps to delete DD files by manufacturer, type, or revision.

Online configuration

Performing configuration, calibration, monitoring, and diagnostics via active link.

Offline configuration

Configuring a device offline using a template.

Online Configuration Overview

Functions for performing operations on a device with an active link.

Detecting and loading a device

Process of detecting and loading a device in FDC.

Overview of Device Homepage

Navigating the device homepage tabs (Information, Functions, My Views, Tools).

Tabs on the Device Homepage

Detailed explanation of each tab on the device homepage.

Using FDC for various device operations

Performing operations like configuration, calibration, monitoring, and diagnostics.

Device Configuration and Parameter Descriptions

Lists and describes parameters accessed via Online tab or Shortcuts menu.

Procedure to Enter the Transmitter Tag

Steps to enter or edit the transmitter tag name.

Selecting the Process Variable (PV) Unit of Pressure Measurement

How to change PV units and its effect on LRV/URV.

Setting PV URV, and LRV Range Values

Procedure to key in LRV and URV values for transmitter calibration.

Setting Range Values for Applied Pressure

Setting range values using applied pressure methods.

Saving device history

Saving device configuration snapshot as history for asset management.

Exporting device history records to FDM

Exporting history records to FDM for audit purposes.

Exporting device history records to Documint

Exporting history records to DocuMint.

Custom Views

Creating and modifying custom views for device variables.

Offline Configuration

Configuring a device offline using a template.

Importing offline configuration

Steps to import offline configuration templates from FDM.

Downloading an offline configuration

Downloading an offline configuration to an online device.

DE Calibration for ST 700 Standard Transmitter

Overview

Discusses transmitter calibration needs and environment.

Calibration Recommendations

Recommends bench calibration with MC Toolkit or using TPS system.

Test Equipment Required for Calibration

Lists necessary test equipment for calibration.

Analog Output Signal Calibration

Procedure for calibrating the analog output signal at zero and 100% levels.

Calibrating Range Using the MC Toolkit

Provides procedures for input and output calibration.

Conditions for Input Calibration

Conditions necessary for accurate transmitter input calibration.

Input Calibration Procedures Description

Describes the three parts of input calibration: zero, LRV, and URV.

Input Calibration Procedure

Step-by-step guide to correct input at zero, LRV, and URV.

DE Output Calibration

Procedure for calibrating DE transmitter's analog output.

Output Calibration Preparation

Preparation steps for DE analog output calibration.

Manually Setting the Process Variable Range

Procedure to manually set PV LRV and URV values.

Procedure to Reset Calibration

Steps to reset calibration data to factory default values.

HART Calibration for ST 700 Standard Transmitter

About This Section

Information on calibrating analog output and range, and resetting calibration.

About Calibration

Discusses calibration needs and recommendations for accuracy.

Equipment Required

Lists test equipment needed for HART calibration.

Analog Output Signal Calibration

Calibrating the transmitter's analog output at 0% and 100% levels.

Calibrating Range

Explains two-point calibration for adjusting all points in a range.

Correcting the Lower Range Value (LRV)

Procedure for correcting the Lower Range Value.

Correcting the Upper Range Value (URV)

Procedure for correcting the Upper Range Value.

Resetting Calibration

Steps to reset calibration data to factory calibrated range.

Calibration Records

How to read calibration records for HART devices.

HART Advanced Diagnostics for ST 700 Standard Transmitter

About This Section

Information on Advanced Diagnostic features of the ST 700 Standard Transmitter.

Advanced Diagnostics

Lists various diagnostics that can be viewed.

Install Date

Details how to view and set the device installation date.

PV Tracking Diagnostics

Information on Maximum and Minimum PV Tracking diagnostics.

SV Tracking

Information on Maximum and Minimum SV Tracking diagnostics.

TV Tracking Diagnostics

Information on Maximum and Minimum TV Tracking diagnostics.

ET Tracking Diagnostics

Information on Maximum and Minimum ET Tracking diagnostics.

% Stress Life

Percent of service life spent in stressful conditions.

% Service Life

Percent of expected service life based on electronics temperature.

Operating Voltage Diagnostics

Diagnostics for current and minimum operating voltage.

AVDD Tracking Diagnostics

Tracking diagnostics for Sensor Supply Voltage.

Sensor CPU Temperature Tracking Diagnostics

Tracking diagnostics for Sensor CPU Temperature.

Power Up Diagnostics

Diagnostics related to device power-ups and last power fail time.

Troubleshooting and Maintenance for ST 700 Standard Transmitter

HART Diagnostic Messages

Lists critical and non-critical HART diagnostic messages.

HART Diagnostic Details

Describes HART critical and non-critical diagnostic details and resolutions.

DE Diagnostic Messages

Lists and describes DE diagnostics and their resolutions.

Using DTMs

Introduction

Introduces DTMs for ST 700 HART/Fieldbus models on Pactware/FDM.

Components

Lists required components for using HART DTMs.

Downloads

Provides download links for Pactware, HART DTM, and Honeywell HART DTM Library.

Procedure to Install and Run the DTM

Step-by-step guide to install and run the DTM.

ST 700 Online Parameterization

Shows the DTM homepage after selecting parameterization.

Device Health

Displays overall device status image and link to status screen.

Process Variables

Shows primary variables, gauges, LRV, and URV.

Shortcuts

Provides tabs for accessing functions like Setup, Calibration, and Status.

Basic Setup Page

Details parameters on the Basic Setup page like Transfer Fn and Device Info.

Pressure Transfer Fn

Allows selection of Linear or Square Root transfer function.

Low Flow Cutoff Mode

Allows selection of User Config Mode and breakpoint for signal conditioning.

Device Information

Provides access to read-only and read/write parameters.

Calibration Page

Provides access to calibration methods and records.

Calibration Methods

Lists available calibration methods like Apply Values, D/A Trim.

Calibration Records

How to access calibration records for URV, LRV, Zero Trim, and Reset Corrects.

Process Variables

Graphical representation of process variables and access to trend charts.

Trend Charts

Displays trend charts for process variables.

Device Status

Shows critical/non-critical status and context-sensitive help.

Critical and Non-Critical Help Display

Displays help for critical/non-critical statuses.

Diagnostics

Access to Advanced Diagnostics and Config History functions.

Services

Allows configuration of Tamper Alarm and Write Protect mode.

Detailed Setup

Shows Sensor Limits, Output Condition, Signal Condition, and Burnout levels.

Meterbody Selection

Details material of construction for Meter Body.

Display Setup

Allows configuring the display from the host.

Screen Configuration

Configures display screens and parameters.

Review

Summary screen showing all parameters.

ST 700 Offline Parameterization

Opens the offline parameter configuration page.

HART DD binary file format compatibility matrix for ST 700 Standard Transmitter

Introduction for ST 700 Basic Transmitter

Features and Options

Lists protocols, HMI, materials, approvals, and mounting brackets for Basic model.

Physical Characteristics

Describes the major assemblies (Electronics Housing, Meter Body) for Basic model.

Functional Characteristics

Explains the Basic transmitter's function and communication protocols.

Series, Model and Number

Details the model number format and identification for Basic transmitter.

Safety Certification Information

Locates and describes the approvals name plate for compliance.

Transmitter Adjustments

Explains adjustments for Basic transmitter using two-button assembly or tools.

Local Display Options

Details the characteristics of the standard display for Basic transmitter.

Integrated 2-Push Button Assembly (Standard Display)

Lists features and capabilities of the 2-button assembly for Basic model.

Communication Modes for ST 700 Basic Transmitter

Overview

Explains HART communication for the Basic transmitter.

HART Mode Communication

Explains HART protocol modes and features for Basic transmitter.

Configuration Tools and Interfaces for ST 700 Basic Transmitter

Overview

Introduces tools for configuring HART operation for Basic transmitter.

Pre-requisites

Assumes user knowledge of MC Toolkit/MCT404/202 and Basic transmitters.

Application Design, Installation, Startup and Operation

Refers to another manual for design, installation, and startup details.

MC Toolkit Participation

Explains prerequisites and potential consequences of using MC Toolkit for Basic transmitter.

MC Toolkit Software Applications

Describes FDC application for HART configuration of Basic transmitters.

Configuration Databases

Explains use of MC Toolkit for parameters in Basic transmitter database.

Configuration

Details online and offline configuration methods for Basic transmitter.

HART Transmitter Configuration for ST 700 Basic Transmitter

Overview

Introduces HART configuration using FDC for Basic transmitter.

Overview of FDC Homepage

Explains FDC homepage links for configuration options for Basic transmitter.

Settings

Customizing FDC for device detection, DD selection, and settings for Basic transmitter.

Device Identification

Options for FDC to identify a device using Poll Address or Device TAG for Basic transmitter.

DD selection

Configuring FDC to select DD files for Basic transmitter.

Manage DDs

Managing DD files for Basic transmitter.

Add a DD file

Steps to add a DD file to FDC for a Basic transmitter.

Delete a DD file

Steps to delete DD files for Basic transmitter.

Offline configuration

Configuring a device offline using a template for Basic transmitter.

Online Configuration Overview

Functions for operations on a device with an active link for Basic transmitter.

Detecting and loading a device

Process of detecting and loading a device in FDC for Basic transmitter.

Overview of Device Homepage

Navigating device homepage tabs for Basic transmitter.

Tabs on the Device Homepage

Detailed explanation of tabs on the device homepage for Basic transmitter.

HART Calibration for ST 700 Basic Transmitter

About This Section

Information on calibrating analog output and range for Basic transmitter.

About Calibration

Discusses calibration needs and recommendations for accuracy for Basic transmitter.

Equipment Required

Lists test equipment for Basic transmitter calibration.

Analog Output Signal Calibration

Calibrating the Basic transmitter's analog output at 0% and 100% levels.

Calibrating Range

Explains two-point calibration for Basic transmitter range adjustment.

Correcting the Lower Range Value (LRV)

Procedure for correcting the Lower Range Value for Basic transmitter.

Correcting the Upper Range Value (URV)

Procedure for correcting the Upper Range Value for Basic transmitter.

Resetting Calibration

Steps to reset calibration data to factory default values for Basic transmitter.

Calibration Records

How to read calibration records for Basic HART devices.

HART Advanced Diagnostics for ST 700 Basic Transmitter

About This Section

Information on Advanced Diagnostic features of the ST 700 Basic Transmitter.

Advanced Diagnostics

Lists various diagnostics that can be viewed for Basic transmitter.

Install Date

Details how to view and set the device installation date for Basic transmitter.

PV Tracking Diagnostics

Information on Maximum and Minimum PV Tracking diagnostics for Basic transmitter.

SV Tracking

Information on Maximum and Minimum SV Tracking diagnostics for Basic transmitter.

TV Tracking Diagnostics

Information on Maximum and Minimum TV Tracking diagnostics for Basic transmitter.

ET Tracking Diagnostics

Information on Maximum and Minimum ET Tracking diagnostics for Basic transmitter.

Troubleshooting and Maintenance for ST 700 Basic Transmitter

HART Diagnostic Messages

Lists critical and non-critical HART diagnostic messages for Basic transmitter.

HART Diagnostic Details

Describes HART critical and non-critical diagnostic details and resolutions for Basic transmitter.

Using DTMs for ST 700 Basic Transmitter

Introduction

Introduces DTMs for ST 700 Basic HART models on Pactware/FDM.

Components

Lists required components for using HART DTMs for Basic transmitter.

Downloads

Provides download links for Pactware, HART DTM for Basic transmitter.

Procedure to Install and Run the DTM

Step-by-step guide to install and run the DTM for Basic transmitter.

ST 700 Online Parameterization

Shows the DTM homepage after selecting parameterization for Basic transmitter.

Device Health

Displays overall device status image and link to status screen for Basic transmitter.

Process Variables

Shows primary variables, gauges, LRV, and URV for Basic transmitter.

Shortcuts

Provides tabs for accessing functions like Setup, Calibration for Basic transmitter.

Basic Setup Page

Details parameters on the Basic Setup page for Basic transmitter.

Pressure Transfer Fn

Allows selection of Linear or Square Root transfer function for Basic transmitter.

Low Flow Cutoff Mode

Allows selection of User Config Mode for Basic transmitter.

Device Information

Provides access to parameters for Basic transmitter.

Calibration Page

Provides access to calibration methods and records for Basic transmitter.

Calibration Methods

Lists available calibration methods for Basic transmitter.

Calibration Records

How to access calibration records for Basic transmitter.

Process Variables

Graphical representation of process variables for Basic transmitter.

Device Status

Shows critical/non-critical status and help for Basic transmitter.

Diagnostics

Access to Advanced Diagnostics and Config History for Basic transmitter.

Services

Allows configuration of Tamper Alarm and Write Protect mode for Basic transmitter.

Detailed Setup

Shows Sensor Limits, Output Condition, Signal Condition for Basic transmitter.

Meterbody Selection

Details material of construction for Meter Body for Basic transmitter.

Display Setup

Allows configuring the display from the host for Basic transmitter.

Screen Configuration

Configures display screens and parameters for Basic transmitter.

Review

Summary screen showing all parameters for Basic transmitter.

HART DD binary file format compatibility matrix for ST 700 Standard Transmitter

Glossary

INDEX