Page 62 ST 700 Series HART/DE Option User’s Manual Revision 4.0
7.5.3.3 Correct Input at URV
1. Click the Correct URV button. This message appears.
2. Adjust the PV input pressure to the exact value of the URV entered in the DE
CONFIGURE display.
3. Click the OK button.
4. When the transmitter has completed the URV correction, the following message appears:
5. Click OK to acknowledge.