Page 156 ST 700 Series HART/DE Option User’s Manual Revision 4.0
18.2.4 TV Tracking Diagnostics
Table 43 – TV Tracking Diagnostics
Static Pressure upper operating limit
specification.
Units are always PSI (pounds per square
inch).
Highest SP ever experienced by the
device.
Units are always PSI (pounds per square
inch).
Backup once each 8 hour period
Time Above
Upper Stress
Limit
Accumulation of minutes that device’s SP
has been above the value of “SP Upper
Stress Limit”.
Backup once each 8 hour period
Time that has passed since the last time
device’s SP has passed above the value of
“SP Upper Stress Limit” (in days, hours,
and minutes).
Backup once each 8 hour period
18.2.5 ET Tracking Diagnostics
Table 44 – Maximum ET Diagnostics
Electronics Temperature (ET) upper
operating limit from specification.
Units are same degree units as has been
selected for SV (Secondary Variable).
ET Upper
Limit for
Stress
Condition
Actual limit used in “Time Above Limit” and
“Time Since Last Event”. Value is equal
to “Max ET Limit” less 10% of limits range.
Electronics Temperature range is -40F to
185F for a total of 225F.
ET Upper Stress Limit= 185F - 10% of
225F = 162.5F.
None: calculation is automatic.
Highest Electronics Temperature ever
experienced by the device.
Units are same degree units as has been
selected for SV (Secondary Variable).
Time Above
Upper Stress
Limit
Accumulation of minutes that device’s
Electronics Temperature has been above
the value of “ET Upper Stress Limit”.
Backup once each 8 hour period