Revision 4.0 ST 700 Series HART/DE Option User’s Manual Page 115
13.5 Local Display Options
The ST 700 Basic SmartLine Pressure Transmitter offers a standard display, see Table 32
Table 32 – Available Display Characteristics
Has a limited character display
360
o
rotation in 90
o
Increments
2 lines, 6 characters
Standard units of measurement: Pa, KPa, MPa, KGcm2, TORR, ATM, inH2O,
mH2O, bar, mbar, inHg, FTH2O, mmH2O, MMHG, & PSI,cmH2O and mH2O
Diagnostic messaging
13.6 Integrated 2-Push Button Assembly (Standard Display)
The Standard Display does not support all the transmitter configurations and has limited features. The
integrated 2-Button Assembly for the Standard Display provides the following features and
capabilities:
Menu and enter key functionality.
With the menu-driven display:
o Comprehensive on-screen menu for navigation.
o Transmitter configuration: enter LRV, enter URV and Loop Test.
o Transmitter calibration
o Display configuration
o Set zero and span parameters.
If you are using the external optional 2-button assembly with the Standard
Display then you can perform all the above operations without removing
external glass cap through the external buttons.
Lower range value (LRV): A display parameter (Standard display), which
allows users to enter the measuring value for which the analog output will
be scaled to 4mA.
Upper range value (URV): A display parameter (Standard display), which
allows users to enter the measuring value for which the analog output will
be scaled to 20mA.