Page 166 ST 700 Series HART/DE Option User’s Manual Revision 4.0
Non critical status
(Warning)
(continued)
Meter Body Unreliable
Comm
Either the transmitter is installed in a noisy
environment or internal communication
quality between the Electronics Module and
Sensor is degrading.
Resolution:
Call service person.
Possible causes:
If this is observed frequently, it is an early
indication of critical under/over-current
failure.
Resolution:
Closely monitor the device status for
indications of other failures, or proactively
replace the Electronics module.
Calculated Analog output is either above or
below the specified Loop Current Limits. The
transmitter input is not in specified range.
Resolution:
Check the transmitter input and verify the
configured operating range.
URV Set Err. Span
Config Button
SET URV operation using external Span
button was rejected.
Resolution:
Verify the inputs are valid for the intended
operation.
LRV Set Err. Zero Config
Button
SET LRV operation using external Zero
button was rejected.
Resolution:
Verify the inputs are valid for the intended
operation.