EasyManuals Logo

Honeywell Spyder PUL1012S User Manual

Honeywell Spyder PUL1012S
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
11 63-2685—03
Fig. 13. Power wiring details for two or more controllers per transformer.
Communications
Refer to “LONWORKS® Wiring Guidelines,” form 74-2865, for a
complete description of L
ONWORKS® Bus network topology
rules and approved cable types.
Honeywell provided cable types for L
ONWORKS® Bus
communications wiring are Level IV 22 AWG (0.34 sq mm)
plenum or non-plenum rated unshielded, twisted pair, stranded
conductor wire.
For non-plenum areas, U.S. part AK3798 (single-pair
stranded) can be used.
In plenum areas, U.S. part AK3797 (single-pair stranded) or
U.S. part AK3799 (two-pair stranded) can be used.
Contact Echelon Corp. Technical Support for the
recommended vendors of Echelon approved cables.
Communications wiring can be run in a conduit, if needed, with
non-switched 24 Vac or sensor wiring. If a longer L
ONWORKS®
Bus network is required, a Q7751A,B router (configured as a
repeater) can be added to extend the length of the
L
ONWORKS® Bus. Each network segment can have a
maximum of one repeater.
Pull the cable to each controller on the L
ONWORKS® Bus and
connect to the controller’s communication terminals 7 and 8.
(See Table 6 on page 13 and Table 7 on page 13, and Fig. 16
on page 14 for location of terminals 7 and 8.)
NOTE: Connection for operator access to the L
ONWORKS®
Bus is provided by plugging the Serial L
ONTALK®
Adapter (SLTA) connector into the L
ONWORKS® Bus
jack (see Fig. 16 on page 14).
IMPORTANT
Notes on communications wiring:
All field wiring must conform to local codes and
ordinances (or as specified on installation drawings).
Do not bundle device output wires with sensor, digital
input or communications L
ONWORKS® Bus wires.
Do not use different wire types or gauges on the
same LONWORKS Bus segment. The step change in
line impedance characteristics causes unpredictable
reflections on the LONWORKS® Bus.
In noisy (high EMI) environments, avoid wire runs
parallel to noisy power cables, motor control centers,
or lines containing lighting dimmer switches. Keep at
least 3 in. (76 mm) of separation between noisy lines
and the L
ONWORKS® Bus cable.
The theoretical limit for each L
ONWORKS® Bus seg-
ment is 60 controllers. Up to 120 controllers can be
configured when a repeater is used, and the bus must
be either singly or doubly terminated. Actual installa-
tions may have a lower limit depending on the
devices connected.
The singly terminated bus must have one 209541B
FTT Termination Module for T tap or Star configura-
tions.
The doubly terminated bus must have two 209541B
FTT Termination Modules, one at each end of the
daisy chain (Bus style) wiring run. Note that the
Q7751A,B router (configured as a repeater) has
onboard terminating networks that can be jumper-
selected on each segment.
Make sure that neither of the L
ONWORKS® Bus wires
are grounded.
NOTE: If a 209541B Termination Module is required at the
controller, connect two of the three termination
module wires to the L
ONWORKS® Bus terminals 7 and
8, which are labeled Net-1 and Net-2, on the
controller. Selecting the appropriate two wires
depends on the L
ONWORKS® Bus network topology.
Refer to the “L
ONWORKS® Bus Wiring Guidelines,”
form 74-2865, and the “FTT Termination Module
Installation Instructions,” form 95-7554. For example,
on a doubly terminated daisy-chained bus topology,
where controllers are on either end of an L
ONWORKS®
Bus wire run, mount the termination module on the
appropriate terminals, as shown in Fig. 14.
M23559A
120/240
VAC
TRANSFORMER
OUTPUT
DEVICE
POWER
ΔP
1
2
3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1
2
3 4
5
6
7 8
0
9
2
2 2
2 2
2
2
2 2
3
3
1
2
3 4
5
6
7 8
0
9
3
3
3
3 3
3 3
3 4
COM
24 VAC
ΔP
1
2
3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1
2
3 4
5
6
7 8
0
9
2
2 2
2 2
2
2
2 2
3
3
1
2
3 4
5
6
7 8
0
9
3
3
3
3 3
3 3
3 4
EARTH
GROUND (TERMINAL 3)
ΔP
1
2
3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1
2
3 4
5
6
7 8
0
9
2
2 2
2 2
2
2
2 2
3
3
1
2
3 4
5
6
7 8
0
9
3
3
3
3 3
3 3
3 4
EARTH
GROUND (TERMINAL 3)
EARTH
GROUND (TERMINAL 3)
CONNECT POWER TO
TERMINALS 1 AND 2

Other manuals for Honeywell Spyder PUL1012S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Spyder PUL1012S and is the answer not in the manual?

Honeywell Spyder PUL1012S Specifications

General IconGeneral
BrandHoneywell
ModelSpyder PUL1012S
CategoryController
LanguageEnglish

Related product manuals