Honeywell T6 Pro Hydronic
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
Wiring terminal designations
S
Input for auxiliary wired floor
or indoor sensors
L/A
- A
Unused
S O/B Unused
Y Unused
AUX
- W2
Unused
Y2 Unused E Unused
G Unused W Heat relay (stage 1)
C
24 VAC common. If a second
transformer, separate
from the one powering the
heating equipment, is used,
use the common from that
transformer.
K Unused
U
Unused
R
24 VAC power from heating
transformer*
U Rc
24 VAC power is a
transformer other than a
heating transformer used to
power display (optional)
* Terminal can be jumped using Slider Tab. See “Setting Slider Tabs” on
page 3.
Heat-only System (with floor sensor)
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24 VAC common [3]
W Heat relay
S,S Input for wired floor sensor
Heat-only System (power open zone
valve)
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24 VAC common [3]
W Valve
Heat-only System (hot water relay
panel with floor sensor)
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24 VAC common [3]
W to W on zone of relay panel
S,S Input for wired floor sensor
Heat-only System (boiler with floor
sensor)
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24 VAC common [3]
W to W on boiler
S,S Input for wired floor sensor
Wiring conventional systems
NOTES
Wire specifications: Use 18 to 22-gauge thermostat wire. Shielded cable is not
required.
[1]
Power supply. Provide disconnect means and overload protection as required.
[2] Move RSlider Tab on UWP to the R (1 wire) setting. For more information,
see “Setting Slider Tabs” on page 3.
[3]
Optional 24 VAC common connection.