T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
63-4355—213
Table 8. Thermostat Installer Setup Options
(Continued).
Installer
Setup Number
(Press
Unoccupied
Temp key
Factory Setting
Other Choices
(Press ▲ or ▼ key to change)
Actual
Select
to change)
Display Description Display Description
Setting
Interstage
control point
(T7300F,
Q7300C,D
only).
31 0 Disabled. 1 thru 12 Temperature has to change more
than the chosen value before the
system calls for the next stage.
(Example: 68°F (20°C) is the heat
setpoint, 2°F (1.1°C) is the
interstage setting, temperature is
65.5°F (18.5°C), the second stage
turns on, brings the temperature to
66°F (19°C) and turns off. The heat
pump continues to run until the
setpoint is met.
Minimum on-
time (T7300F).
32 2 2-minute minimum on-
time for heating and
cooling.
0 or 1 No minimum on-time or
1-minute minimum on-time for
heating and cooling.
Minimum off -
time for the
compressor.
33 4 4-minute minimum off-
time for the
compressor.
0, 1, 2, 3
or 5
Minimum number of minutes
(0 thru 5) the compressor is off
between calls for the compressor.
Temperature
range stops in
heating
(T7300F).
34 90 Highest heating
setpoint.
40 to 89 Temperature range (1°F
increments) for heating setpoint.
Temperature
range stops in
cooling
(T7300F).
35 45 Lowest cooling
setpoint.
46 to 99 Temperature range (1°F
increments) for cooling setpoint.
Not used. 36 — — — — —
Temperature
display
adjustment.
37 0 No difference in
displayed temperature
and actual room
temperature.
1 thru 6 1—Display adjusts to 1°F (0.6°C)
higher than actual room
temperature.
2—Display adjusts to 2°F (1.1°C)
higher than actual room
temperature.
3—Display adjusts to 3°F (1.7°C)
higher than actual room
temperature.
4—Display adjusts to 1°F (0.6°C)
lower than actual room
temperature.
5—Display adjusts to 2°F (1.1°C)
lower than actual room
temperature.
6—Display adjusts to 3°F (1.7°C)
lower than actual room
temperature.
Minimum off-
times in heating.
38 4 4—4-minute minimum
off-time
0, 1, 2, 3,
or 5
Minimum number of minutes
(0 thru 5) the heating equipment is
off between calls for heat.
Not used. 39 — — — — —
Installer Setup
lockout (keypad
lockout is
enabled and
disabled by DIP
switch 1 on
back of
thermostat).
40 0 0—No Installer Setup
lockout.
1 1—Installer Setup lockout
activated.