V4730C/V8730C/V4734C 1:1 Gas/Air Servo Regulated Gas Valves
EN2R-9074 0612R1-NE 15
OPERATION
The V4730C/V8730C/V4734C are normally closed valves. The 
valves open when energized and close when power is removed.
1. Do not put the system into service until you have satisfactorily
completed the Valve Leak Test, all applicable tests described
in the Checkout section of the instructions for the flame safe-
guard control, and any other tests required by the burner ma-
nufacturer.
2. All tests must be performed by a trained, experienced, flame 
safeguard technician.
3. Close all manual fuel shutoff valves immediately if trouble oc-
curs.
After the installation is complete, cycle the valve several times 
with the manual fuel shutoff valve cock closed. Make sure the val-
ve functions properly. Also, perform the Valve Leak Test before 
putting the valve into service.
Valve Leak Test (Fig. 19)
This is a test for checking the closure tightness of the gas shutoff 
valve. It should be performed only by trained, experienced, flame 
safeguard technicians during the initial startup of the burner sys-
tem or whenever the valve is replaced. It is recommended that 
this test should also be included in the scheduled inspection and 
maintenance procedures. For a periodic inspection test, follow 
steps 1, 3, 4, 5, 8, 9, 10, 12, 13, 17, and 18.
1. De-energize the control system to make sure no power goes
to the valves.
2. Close the upstream manual gas cock (A).
3. Make sure the manual test petcock (F) is closed in the leak 
test tap assembly.
4. To test the first SSOV, remove the 1/8 in. (3mm) NPT plug 
from pressure tap point P.
5. Install the leak test tap into pressure tap point P on the valve 
body.
6. Open the upstream manual gas cock (A) to repressurize the 
first SSOV.
7. Immerse the 1/4 in. (6 mm) tube vertically 1/2 in. (13 mm) in 
a jar of water.
8. Slowly open the manual test petcock (F).
9. When the rate of bubbles coming through the water stabili-
zes, count the number of bubbles appearing during a ten-se-
cond period. Each bubble appearing represents a flow rate of 
0.001 cfh (28 cch). See Table 4.
10. Close the upstream manual gas cock (A).
11. Remove the leak test tap from the valve body.
12. Using a small amount of pipe sealant on the 1/8 in. (3 mm) 
NPT plug, reinstall the plug in pressure tap point P
13. To test the second SSOV, remove the 1/8 in. (3 mm) NPT 
plug from the flange pressure tap point 4.
14. Install the leak test tap into pressure tap point 4.
15. Close the downstream manual gas cock (E).
16. Energize the first SSOV
Table 4: max. bubbles per pipe size
17. Immerse the 1/4 in. (6 mm) tube vertically 1/2 in. (13mm) into 
a jar of water.
18. Slowly open the manual test petcock (F).
19. When the rate of bubbles coming through the water stabili-
zes, count the number of bubbles appearing during a ten-se-
cond period. Each bubble appearing during a 10-second 
period represents a flow rate of 0.001 cfh (28 cch). 
See Table 4.
20. De-energize First SSOV
21. Remove the leak test tap from the valve body.
22. Using a small amount of pipe sealant on the 1/8 in. (3 mm) 
NPT plug, reinstall the plug in pressure tap point 4.
Fig. 19: Valve leak test
After the Test
1. . Make sure the downstream manual gas cock (E) is closed.
2. Open the upstream manual gas cock (A) and energize the 
valve through the safety system.
3. Test with rich soap and water solution to make sure there is 
no leak at the test tap (D) or any pipe adapter/valve mating 
surfaces.
4. De-energize the valve (C).
5. Open the downstream manual gas cock (E).
6. Restore the system to normal operation.
WARNING
Explosion and Electrical Shock Hazard. Can cau-
se severe injury, death or property damage.
WARNING
Electrical Shock Hazard. Can cause severe injury 
or death.
Remove the power from the system before beginning 
the valve leak test to prevent electrical shock. More 
than one disconnect may be involved.
Pipe Size (in. NPT) Maximum Seat 
Leakage (UL)
Maximum Number 
of Bubbles in 10 
seconds
1/2 - 3/4 235 cch 6
1 275 cch 7
1 - 1/4 340 cch 8