VISTA-128BP/VISTA-250BP Installation and Setup Guide
5-12
FIELD
TITLE and DATA ENTRIES EXPLANATION
1*60
Zone 5 Audio Alarm Verification
0 = disable
1 = enable
If enabled, zone 5 is used for 2-way audio (AAV).
Must be 0 for UL installations.
NOTE: Zone 5 cannot be used as protection zone.
1*69
Printer Type
0 = parallel printer
1 = serial printer
Select the printer type for the event log printout.
NOTE: if you are using a parallel printer connected to the VA8201 Alpha Pager
Module.
1*70
Event Log Types
0 = disable
1 = enable
This field has five entries as follows: Alarm, Check, Bypass, Open/Close,
System. If enabled, the system logs those events into the event log.
NOTE: Events are also logged into the PassPoint system, if installed.
1*71
12/24 Hour Type Stamp Format
0 = 12-hour
1 = 24-hour
Select the type of time stamping for the event log.
1*72
Event Log Printer On-Line Mode
0 = disable
1 = enable
If enabled, the system prints the events as they occur.
If disabled, the system prints the log only upon request.
1*73
Printer Baud Rate
0 = 1200
1 = 300
Select the baud rate for the serial printer.
NOTE: Must be 1 if using the alphanumeric pager interface.
1*74
Relay Timeout XXX Minutes
Enter 000-127 times 2 minutes (000-254).
This is used for #80 Menu Mode Time-Driven event relay command numbers
“04/09” and
Output Programming
in the
#93 Menu Mode Programming
output
command “56.”
1*75
Relay Timeout YYY Seconds
Enter 000-127 seconds.
This is used for #80 Menu Mode Time-Driven event relay command numbers
“05/10” and
Output Programming
in the
#93 Menu Mode Programming
command “57.”
1*76
Access Control Relay (partition-
specific)
01-96 = relay number
00 = relay not used.
If enabled, the assigned relay closes for 2 seconds when the user enters his
code and presses 0.
Must be 00 for UL installations.
NOTE: See
SECTION 3: Installing the Control
for enhanced access control
capabilities.
2*00
Number of Partitions
Enter 1-8.
Enter the number of partitions used in the system.
2*01
Daylight Saving Time Start/End
Month
0 = disable
1 = enable
Enter the months (00-12) in which daylight saving time starts and ends.
Enter 00, 00 if daylight saving time does not apply to the user’s region.
Standard setting for U.S. is 04,10.
2*02
Daylight Saving Time Start/End
Weekend
0 = disable
1 = enable
Enter the start and end weekends for daylight saving time as follows: 1=first;
2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last. Standard
setting for U.S. is 1,5.
U
L
Fields 2*05 – 2*08 must be set to 0 for UL installations.