Section 5 – Data Field Descriptions
5-13
FIELD
TITLE and DATA ENTRIES EXPLANATION
2*05
Auto-Arm Delay (partition-
specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto arming.
This is the time between the end of the arming window and the start of auto-arm
warning time (field 2*06).
2*06
Auto-Arm Warning Period
(partition-specific)
01-15 times 1-minute warning.
00 = no warning period.
This is the time that the user is warned by a keypad sounding and display to exit
the premises prior to auto arming of the system.
2*07
Auto-Disarm Delay (partition-
specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto disarming.
This is the time between the end of the disarming window and the start of auto
disarming of the system.
2*08
Force Arm Enable for Auto-Arm
(partition-specific)
0 = disable
1 = enable
If enabled, the system automatically bypasses any faulted zones when it
attempts to auto-arm.
If disabled, the system will not auto-arm.
2*09
Open/Close Reports by
Exception (partition-specific)
0 = disable
1 = enable
If enabled, Open/Close reports are sent only if the openings/closings occur
outside the arm and disarm windows.
NOTES:
Open reports are also suppressed during the closing window in order to prevent
false alarms if the user arms the system, then re-enters the premises, for
example to retrieve a forgotten item.
Openings and closings are still recorded in the event log.
This field must be set to 1 if No Opening and No Closing reports are to be sent.
2*10
Allow Disarming Only During
Arm/Disarm Windows (partition-
specific)
0 = disable
1 = enable
If enabled, disarming of the system is allowed only during the arming/disarming
windows, or if the system is in alarm (if 2*11 is set to 1).
NOTE: This applies only to Operator-level users. Installer, Master, and
Manager-level users can disarm the system at any time.
2*11
Allow Disarm Outside Window if
Alarm Occurs
0 = disable
1 = enable
If enabled, allows the system to be disarmed outside the programmed disarm
(opening) window if an alarm has occurred. Otherwise disarming is allowed only
during the disarm window.
NOTE: Used only if field 2*10 is enabled.
2*18
Enable GOTO for this Partition
(partition-specific)
0 = disable
1 = enable
If enabled, this partition can be accessed from another partitions keypad using
the GOTO command.
2*19
Use Partition Descriptor
0 = disable
1 = enable
If enabled, the normal keypad display will include a partition number and four-
digit descriptor.
2*20
Enable J7 Triggers for Partition
(partition-specific)
0 = disable
1 = enable
If enabled, the J7 triggers function for this partition.