to  either  main  or  pilot  burner. 
PILOT,  which  permits  gas  to  flow  to  pilot  burner 
only  (when  gas  cock  knob  is  held  depressed  or  when 
generator  is  heated  sufficiently  to  hold  valve  open). 
ON,  which  permits  gas  to  flow  to  both  main  and 
pilot  burners  when  the  system  is  calling  for  heat. 
PILOT  LIGHTING  PROCEDURE 
1.  Slightly  depress  Lite-Rite  knob  if  at  PILOT 
position  and  turn  clockwise  m  to  OFF.  Wait  5 
minutes  for  all  unburned  gas  to  vent.  REMEMBER 
that  LP  gas  does  not  vent  upward  naturally. 
2.  Turn  the  Lite-Rite  knob  to  PILOT,  depress  it 
completely,  and  light  the  pilot  burner.  The  knob  must 
be  held  down  about  one  minute  before  the  pilot 
burner  will  stay  lit  after  releasing  the  knob. 
3.  Turn  the  knob  to  ON,  and  set  the  thermostat 
above  room  temperature  to  turn  on  main  burner. 
TEST  FOR  GAS  LEAKS 
WARNING  -  DO  NOT  OMIT  THIS  TEST 
With  main  burner  in  operation,  paint  pipe  joints, 
pilot  gas  tubing  connections,  and  valve  gasket  lines 
with  rich  soap  and  water  solution.  Bubbles  indicate 
gas  leakage.  To stop  leak,  tighten  joints  and  screws 
or  replace  the  gasket. 
ADJUST  PILOT  FLAME 
The  pilot  flame  should  envelop  3/8  to  l/2 
inch  of  the  tip  of  the  thermocouple.  Remove 
pilot  adjustment  cover  screw  (refer  to  Fig.  1). 
Turn  inner  adjustment  screw  clockwise  mto 
decrease  or  counterclockwise  n  to  increase 
pilot  flame.  Be  sure  to  replace  cover  after 
adjustment  to  prevent  possible  gas  leakage. 
PROPER 
3/S  TO  112  INCH 
CHECK  GAS  INPUT  TO  APPLIANCE 
IMPORTANT 
Do  not  exceed  input  rating  stamped  on 
nameplate  of  appliance,  or  manufacturer’s 
recommended  burner  orifice  pressure  for  size 
orifice(s)  used.  Make  certain  primary  air  supply 
to  main  burner  is  properly  adjusted  for  complete 
combustion.  Follow  instructions  of  appliance 
manufacturer  if  provided. 
NOTE:  IF  METER  CLOCKING  METHOD  IS  USED 
Make  certain  there  is  no  gas  flow  through  the 
meter  other  than  to  the  appliance  being  checked. 
Other  appliances  must  remain  off,  and  the  pilot 
extinguished  (or  their  consumption  deducted  from 
the  meter  reading). 
‘A”  MODEL  PROCEDURE  (with  pressure  regulator) 
1.  Check  input  to  main  burner  by  clocking  gas 
meter  or  by  using  a  pressure  gauge  (manometer) 
connected  to  downstream  tapping  (Fig.  1).  The 
standard  natural  gas  model  is  factory  set  at  3.5 
inches  WC  outlet  pressure,  and  the  standard  LP  gas 
model  is  set  at  11  inches.  If  adjustment  is  required, 
proceed  with  step  2. 
2.  Remove  cover  screw  (see  Fig.  1).  Using 
screwdriver,  turn  adjusting  screw  clockwise  m  to 
increase  or  counterclockwise  n  to  decrease  gas 
pressure  to  burner.  (Note:  Adjustment  fitting  is 
plastic  and  may  require  slightly  greater  turning  force 
than  metal  thread.)  Replace  cover  screw. 
“B”  MODEL  PROCEDURE  (no  pressure  regulator) 
1.  With  main  burner  off,  connect  pressure  gauge 
(manometer)  to  downstream  pressure  tapping  (Fig.  1). 
2.  With  main  burner  operating,  check  burner 
manifold  pressure. 
3.  If  pressure  is  not  as  specified  by  the  appliance 
manufacturer,  readjust  regulator  on  LP  gas  storage 
tank. 
STEP-OPENING  PRESSURE  REGULATOR 
1°C”  MODELS) 
1.  With  main  burner  operating,  check  input  by 
clocking  gas  meter,  or  check  burner  manifold 
pressure  using  pressure  gauge  (manometer) 
connected  to  downstream  pressure  tapping  (Fig.  1). 
2.  If  adjustment  is  required,  remove  cover  screw. 
Using  a  small  screwdriver,  turn  adjusting  screw 
clockwise  m  to  increase  or  counterclockwise 
n  to  decrease  gas  pressure  to  burner.  Replace 
cover  screw. 
3.  Check  burner  performance  at  step  pressure, 
observing  burner  ignition  and  flame  characteristics. 
Burner  should  ignite  properly  and  without  flashback 
to  orifice,  and  all  ports  should  remain  lit.  Cycle 
burner  several  times  (wait  30  seconds  between 
cycles  to  allow  servo  regulator  to  resume  step 
action.)  Repeat  after  allowing  appliance  to  cool. 
CHECKOUT 
Put  the  system  into  operation  and  observe  through 
complete  cycle  to  be  sure  all  controls  function 
properly.  Make  certain  the  Pilotstat  unit  shuts  off  gas 
flow  to  main  burner  within  2-l/2  minutes  after  pilot 
flame  is  extinguished. 
3