PILOT  GOES  OUT  WHEN  LITE-RITE  KNOB  IS 
RELEASED 
1.  Check  pilot  flame  adjustment.  See page  3. 
2. Check  the  Powerpile  generator  connection  to 
Pilotstat  power  unit  (Fig.  1). This  is an  electrical  con- 
nection  and  must  be clean  and  secure.  Also  check  the 
Powerpile  generator  connections  to  the  valve  operator. 
3.  If power  unit  still  does  not  hold  in,  use  the  W720 
Systems  Tester to  obtain  the  exact  open  and  closed 
circuit  output  voltages  of the  generator.  Compare  with 
the  Acceptable  Range  Charts  in  W720  manual  or Gas 
Controls  Service  Handbook.  Next  check  resistance  of 
Pilotstat  power  unit. 
If W720  or other  meter  is not  available,  first  replace 
generator.  If this  does  not  correct  the  condition 
replace  power  unit  (adjacent  to  gas  cock  knob  -  see 
Fig.  1). Turn  off  gas  supply  to appliance  (at service 
cock  or  meter) and  remove  power  unit  with  wrench. 
Install  and  tighten  new  power  unit.  Turn  on  gas supply 
and  check  for  gas  leakage. 
COMPONENT  AND  PARTS  REPLACEMENT 
The  automatic  valve  operators  and  servo  regulators 
may  be  added  in the  field,  or  replaced  in  service 
maintenance.  (Model  number  is  stamped  on  side  of 
component.)  Complete  instructions  are  furnished  with 
the  component. 
REPLACEMENT  VALVE  OPERATOR:  VS824A. 
REPLACEMENT  SERVO  PRESSURE  REGULATOR: 
V5306  standard  and  V5307  step  opening  type. 
Either  models  are  field  addable  to  “B”  models. 
VS820  “A”  or  “C”  models  can  be  converted  to 
“B”  models  by  removing  the  pressure  regulator  and 
applying  a  blank  plate  and  gasket,  Pt.  No.  392782. 
REPLACEMENT  PARTS: 
Pilotstat  power  unit  (750  mv)  -  392395. 
Compression  fitting  for  pilot  tubing  connection- 
386449. 
Pilot  gas  filter  -  391158. 
OPERATING  INSTRUCTIONS  FOR  THE 
HOMEOWNER 
‘MPORTANT 
Follow  the  operating  instructions  provided  by the 
manufacturer  of your heating  appliance.  The  infor- 
mation  below  will  be of assistance  in a typical  con- 
trol  application,  but the  specific  controls  used  and 
the  procedures  outlined  by  the  manufacturer  of 
your  appliance  may  differ,  requiring  special 
instructions. 
LITE-RITE  KNOB  SETTINGS 
Refer  to  GAS  COCK  SETTINGS,  page  2. 
TO  LIGHT  PILOT  AND  TURN  ON  MAIN  BURNER 
Follow  PILOT  LIGHTING  PROCEDURE,  page  3. 
TO  SHUT  OFF 
1.  For  TEMPORARY  situations:  Main  burner  can  be 
shut  off  by  turning  clockwise  m  from  ON  to 
PILOT.  Pilot  will  remain  lit  -  ready  for  return  to  nor- 
mal  service  without  relighting.  (This  is the  recom- 
mended  summer  shutdown  position.) 
2.  For  COMPLETE  SHUTDOWN:  Slightly  depress 
Lite-Rite  knob  when  at  PILOT  position  and  turn 
clockwise  m  to  OFF  Both  pilot  and  main  burner 
now  are  shut  off. 
AUTOMATIC  SAFETY  SHUTOFF 
The  automatic  safety  shutoff  valve  blocks  gas  flow 
to  the  main  burner  and  pilot  burner  if  the  pilot  flame 
goes  out  or  becomes  too  small  for  adequate  ignition. 
If  safety  shutoff  occurs,  check  pilot  flame  after 
relighting  and  adjust  if  necessary.  See  ADJUST 
PILOT  FLAME,  page  3.  If  shutoff  reoccurs,  contact 
your  local  dealer  or  gas  utility  to  correct  condition 
causing  shutdown. 
ELECTRICAL  DATA: 
Pilotstat  Power  Unit  -  Hold-in  15  ma  maximum; 
dropout  10.5  to  4.5  ma;  resistance  11  ohms. 
Valve  Operator  -  Pull-in  65  ma  maximum;  coil 
resistance  2  ohms. 
This  material  is proprietary  to  Honeywell  Limited  and  shall  not  be reproduced,  copied  or  used  in any  manner  without  prior  written  consent  of 
Honeywell  Limited. 
HONEYWELL  l 740  Ellesmere  Road  l Scarborough  l Ontario  MlP  2V9