XNX Universal Transmitter
Specications
155
EN60079-29-1 Performance Approved Gases for mV Sensor Types
Sensor Type
EN60079-29-1
Reference
Verified Gas Selections
Hydrogen Methane-2 Propane-2 Butane-2 Star 2 Star 4
MPD AMCB1
Standard Test Gas
l l
Other Gases
l l
n-nonane
SP-HT
Standard Test Gas
l l
Other Gases
l l
n-nonane
Max Zero Deviation (see note 1) -7% LEL -9% LEL -7% LEL
LDL (see note 2) 3% LEL 5% LEL 3% LEL
SP-PPM (10%L) 10% LEL
Notes
1. Readings < 0% LEL are not displayed or indicated on the 20 mA output. Values exceeding the zero deviation limit will result in F111 faults.
2. Readings < LDL are shown as 0% on the display and 20 mA output.
Other Sensor Performance Data
Performance data for other supported sensors is available in their respective technical manuals.