The E6040 must be plugged
into CN11 on the control
using the C2023 harness
3rd Step
Set the reversing sensitivity
fully counter-clockwise.
POWER SUPPLY
C3955 for 120VAC
To AutoLock
CN 7
If the day / night mode is
NOT
to be used - there
MUST
be a
jumper between 15 & 16.
See Sections 5 thru 10 for actuating
features and lock set-up.
NOTE:
Do
NOT
wire any motion detectors or
any other accessories at this time.
Factory pre-wired beams (pins 5,6 & 7) may
be left in place.
1.0009d
11-08
2nd Step
16
15
Plug into E6040
Wht
Orn
Blk
Brn
Blu
Red
CN 4
1. SERIES 2000 SLIDE OPERATOR QUICK START INSTRUCTIONS
9th Step
Verify jumpers JB1A & JB1B
ARE REMOVED on rev. E and
later controls.
To get the operator up and running, check the items outlined below-
C2150 Control with version 1software (Revision E or later hardware)
A toggle switch or jumper must
be present between pins 8 & 9.
Switches are sent loose and field
mounted. Break-outs are wired in
series with the toggle switch.
9
8
2000
switch
Optional
switch
CN 2
1st Step
8th Step
The motor must
be plugged into
connector CN8
6th Step
H201C.1
Ground GRN U.S. - GRN / YEL Int.
(Connect to grounding screw)
Check that the incoming power is
wired as shown.
Line (Hot side) BLK U.S. - BRN Int.
Neutral WHT U.S. - BLU Int.
F 3
Motor
+100 to +120
VDC
1
F 2
F
2
F
3
To REED
switches
See pg
H201C.6
CN 2
Grn
Yel
2
3
All fuses are
5x20 mm Type "T"
Rated 3.15 amp
+27 to +35VDC
& processor
F 1
Master
fuse
AC POWER IN
CN 1
A 5 conductor cable attaches CN7
to the power supply.
6th Step
BLK
RED
4th Step
CN 8
TO MOTOR
1 2 3 4 5GND
7th Step
Check incoming voltages
from power supply
+120 to +100
VDC from F2
+27 to + 35
VDC from F3