Page 14 of 27
Run Time per HP UPS Model
Backup times** (in minutes)
T750 G2 and T750 Japan
Load, percent Load, Watts Estimated battery runtime at 100% battery charge
50% 250 15 minutes
100% 500 5 minutes
T1000 G3 and T1000 Japan
Load, percent Load, Watts Estimated battery runtime at 100% battery charge
50% 335 15 minutes
100% 670 5 minutes
T1500 G3 and T1500 Japan
Load, percent Load, Watts Estimated battery runtime at 100% battery charge
50% 475 15 minutes
100% 950 5 minutes
R3000
Load, percent
With Standby Battery With 1 ERM With 2 ERMs
20% 40 minutes 120 minutes 250 minutes
50% 12 minutes 45 minutes 100 minutes
80% 6.5 minutes 30 minutes 60 minutes
100% 5 minutes 20 minutes 40 minutes
R/T3000 Low Volt Models
Load, percent
With Standby Battery With 1 ERM With 2 ERMs
20% 45 minutes 142 minutes 256 minutes
50% 15 minutes 55 minutes 99 minutes
80% 7 minutes 34 minutes 60 minutes
100% 5 minutes 26 minutes 47 minutes
R/T3000 High Volt Models
Load, percent
With Standby Battery With 1 ERM With 2 ERMs
20% 40 minutes 125 minutes 225 minutes
50% 12 minutes 50 minutes 99 minutes
80% 6 minutes 30 minutes 60 minutes
100% 4 minutes 24 minutes 47 minutes