Page 14 of 27 
Run Time per HP UPS Model  
Backup times** (in minutes) 
 
T750 G2 and T750 Japan 
Load, percent  Load, Watts  Estimated battery runtime at 100% battery charge 
50%  250  15 minutes 
100%  500  5 minutes 
 
T1000 G3 and T1000 Japan 
Load, percent  Load, Watts  Estimated battery runtime at 100% battery charge 
50%  335  15 minutes 
100%  670  5 minutes 
 
T1500 G3 and T1500 Japan 
Load, percent  Load, Watts  Estimated battery runtime at 100% battery charge 
50%  475  15 minutes 
100%  950  5 minutes 
 
R3000 
Load, percent 
With Standby Battery   With 1 ERM  With 2 ERMs 
20%  40 minutes   120 minutes  250 minutes 
50%  12 minutes   45 minutes  100 minutes 
80%  6.5 minutes   30 minutes  60 minutes 
100%  5 minutes   20 minutes  40 minutes 
 
R/T3000 Low Volt Models 
Load, percent 
With Standby Battery   With 1 ERM  With 2 ERMs 
20%  45 minutes   142 minutes  256 minutes 
50%  15 minutes   55 minutes  99 minutes 
80%  7 minutes   34 minutes  60 minutes 
100%  5 minutes   26 minutes  47 minutes 
 
R/T3000 High Volt Models 
Load, percent 
With Standby Battery   With 1 ERM  With 2 ERMs 
20%  40 minutes   125 minutes  225 minutes 
50%  12 minutes   50 minutes  99 minutes 
80%  6 minutes   30 minutes  60 minutes 
100%  4 minutes   24 minutes  47 minutes