System Inlet Temperature
System Inlet TemperatureSystem Inlet Temperature
System Inlet Temperature
Operating
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change is
10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed. System performance may be reduced if
operating with a fan fault or above 30°C (86°F).
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Relative Humidity
Relative HumidityRelative Humidity
Relative Humidity
(non-condensing)
Operating
10 to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-
condensing.
Non-operating
5 to 95% relative humidity (Rh), 38.7°C
(101.7°F) maximum wet bulb temperature, non-
condensing.
Altitude
AltitudeAltitude
Altitude
Operating
3050 m (10,000 ft). This value may be limited by
the type and number of options installed.
Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Non-operating
9144 m (30,000 ft). Maximum allowable
altitude change rate is 457 m/min (1500 ft/min).
Acoustic Noise
Acoustic NoiseAcoustic Noise
Acoustic Noise
Listed are the declared A-Weighted sound power levels (LWAd) and declared
average bystander position A-Weighted sound pressure levels (LpAm) when
the product is operating in a 23°C ambient environment. Noise emissions
were measured in accordance with ISO 7779 (ECMA 74) and declared in
accordance with ISO 9296 (ECMA 109).
Idle
depends on server configuration & mix of server
blades
Operating
varies by CPU utilization, server configuration,
and mix of server blades
Enclosure Unit – Tower
Enclosure Unit – TowerEnclosure Unit – Tower
Enclosure Unit – Tower
Model
ModelModel
Model
Dimensions
Dimensions Dimensions
Dimensions
(H x W x D)
(with bezel)
21.29 x 13.48 x 34.43 in (54.08 x 34.24 x 87.45 cm)
Weight
WeightWeight
Weight
(approximate)
Maximum
(all server blades and
interconnects installed)
342 lb (155 kg)
Minimum
(2 power supplies & 4
fans, no server blades nor
interconnects installed)
192 lb (87.09 kg)