Input Requirements
Input RequirementsInput Requirements
Input Requirements
(per AC power supply)
Rated Line Voltage
90
–
––
–
132 VAC
180 - 264 VAC
Rated Input Current
9.3 A (at 100 VAC)
9.7 A (at 110 VAC)
7.8 A (at 200 VAC)
7.2 A (at 208 VAC)
6.8 A (at 220 VAC)
6.2 A (at 240 VAC)
Rated Input Frequency
47 to 63 Hz
BTU Rating
BTU RatingBTU Rating
BTU Rating
Maximum per power
supply
2728 BTU/hr (at 100 VAC)
3069 BTU/hr (at 120VAC)
4092 BTU/hr (at 200 to 240 VAC)
Power Specifications
Power SpecificationsPower Specifications
Power Specifications
To review typical system power ratings use the Power Calculator which is
available via the online tool located at URL: :
www.hp.com/go/bladesystem/powercalculator
Power Supply Output
Power Supply OutputPower Supply Output
Power Supply Output
(per power supply)
Rated Steady-State Power
800 W (at 100 VAC),
900 W (at 120 VAC)
1200 W (at 200 to 240 VAC)
Maximum Peak Power
880 W (at 100 VAC),
990 W (at 120 VAC)
1350 W (at 200 to 240 VAC)
System Inlet Temperature
System Inlet TemperatureSystem Inlet Temperature
System Inlet Temperature
Operating
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change is
10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed. System performance may be reduced if
operating with a fan fault or above 30°C (86°F).
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Relative Humidity
Relative HumidityRelative Humidity
Relative Humidity
(non-condensing)
Operating
10 to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-
condensing.
Non-operating
5 to 95% relative humidity (Rh), 38.7°C
(101.7°F) maximum wet bulb temperature, non-
condensing.
Altitude
AltitudeAltitude
Altitude
Operating
3050 m (10,000 ft). This value may be limited by
the type and number of options installed.
Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Non-operating
9144 m (30,000 ft). Maximum allowable
altitude change rate is 457 m/min (1500 ft/min).
QuickSpecs
HP BladeSystem c3000 Enclosure
HP BladeSystem c3000 EnclosureHP BladeSystem c3000 Enclosure
HP BladeSystem c3000 Enclosure
Technical Specifications
DA - 12790 North America — Version 7 — February 11, 2008
Page 33