Specification Value
Temperature range
Note:
All temperature ratings shown are for sea level. An altitude derating of
1°C per 304.8 m (1.8° per 1,000 ft.) above sea level to a maximum of
3048 m (10,000 ft), no direct sustained sunlight.
Operating 10° to 35°C (50° to 95°F) Maximum rate of change is 10°C/hr (18°F/hr).
The upper limit may be limited by the type and number of options installed.
System performance may be reduced if operating with a fan fault or above
30°C (86°F).
Non-operating -30° to 60°C (-22° to 140°F). Maximum rate of change is 20°C/hr (36°F/hr).
Relative humidity (non-
condensing)
Operating 10 to 90% relative humidity (Rh), 28°C (82.4°F) maximum wet bulb
temperature, non-condensing.
Non-operating 5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb
temperature, non-condensing.
Power requirements
A table listing the power requirements for the HP ProLiant DL360p G8 server.
Table 1: HP 460 W CS power supply (92% efficiency)
Specification
Value
BTU 1053.53 BTU/hr
Voltage 100V — 240V
Plug Type NEMA — 15
Circuit Breaker 15 amp
Pole 1
AMP Draw 2.69 @ 115 VAC
Total Watts 308.95 W
Note:
These numbers are based on the following typical Avaya configuration:
qty=2 – E5-2630 six core processors
qty=8x4 GB– Memory (1Rx4 PC3-12800R-11 kit)
qty=3 – 2.5” SFF SAS HDDs
qty=1 – Flexible LOM 1GB Ethernet network card 4 port 331T
qty=2 – 460W AC power supplies
Power requirements
September 2013 Installing the HP ProLiant DL360p G8 Server 11