HPE ProLiant DL380 Generation9 (Gen9)
Extended Ambient
Operating Support
For approved hardware configurations, the supported system
inlet range is extended to be: 5° to 10°C (41° to 50°F) and
35° to 40°C (95° to 104°F) at sea level with an altitude
derating of 1.0°C per every 175 m (1.8°F per every 574 ft)
above 900 m (2953 ft) to a maximum of 3050 m (10,000 ft).
The approved hardware configurations for this system are
listed at the URL:
http://www.hp.com/servers/Ashrae
For approved hardware configurations, the supported system
inlet range is extended to be: 40° to 45°C (104° to 113°F) at
sea level with an altitude derating of 1.0°C per every 125 m
(1.8°F per every 410 ft) above 900 m (2953 ft) to a maximum
of 3050 m (10,
000 ft). The approved hardware configurations
for this system are listed at the
URL: http://www.hp.com/servers/Ashrae
System performance may be reduced if operating in the
extended ambient operating range or with a fan fault.
-30° to 60°C (-22° to 140°F). Maximum rate of change is
20°C/hr (36°F/hr).
Humidity
Minimum to be the higher (more moisture) of -12°C (10.4°F)
dew point or 8% relative humidity. Maximum to be the lower
(less moisture) of 24°C (75.2°F) dew point or 90% relative
humidity.
5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet
bulb temperature, non-condensing.
3050 m (10,000 ft). This value may be limited by the type and
number of options installed. Maximum allowable altitude change
rate is 457 m/min (1500 ft/min).
9144 m (30,000 ft). Maximum allowable altitude change rate is
457 m/min (1500 ft/min).
Listed are the declared A-Weighted sound power levels (LWAd) and declared
average bystander position A-Weighted sound pressure levels (LpAm) when the
product is operating in a 23°C ambient environment. Noise emissions were
measured in accordance with ISO 7779 (ECMA 74) and declared in accordance
with ISO 9296 (ECMA 109).