HPE ProLiant DL380 Generation9 (Gen9)
SFF Drives: 3.44 x 17.54 x 26.75 in (8.73 x 44.55 x 67.94 cm)
LFF Drives: 3.44 x 17.54 x 28.75 in (8.73 x 44.55 x 73.02 cm)
NOTE:
Dimensions without Bezel.
(approximate)
(Minimum - 8SFF
chassis with 1xSFF
HDD and 7 HDD
blanks, 1x
processor, 1x
blank), 1x Flexible
Smart Array, 1x
(Maximum - 12
LFF hard drives
processors, 2x
power supplies, 1x
Flexible Smart
Array, 2x Risers
Requirements
(per power
For 800W Power Supply: 3207 BTU/hr (at 100 VAC), 3071
BTU/hr (at 200 VAC), 3112 BTU/hr (at 240 VAC) for China
Only
For 500W Power Supply: 1979 BTU/hr (at 100 VAC), 1911
BTU/hr (at 200 VAC), 1965 BTU/hr (at 240 VAC) for China
Only
Output
(per power
supply)
State Power
For 1400W Power Supply: 1400W (at 240 VAC), 1400W (at
240 VAC)
For 800W Power Supply: 800W (at 100 VAC), 800W (at 240
VAC), 800W (at 240 VAC) input for China only
For 500W Power Supply: 500W (at 100 VAC), 500W (at 240
VAC), 500W (at 240 VAC) input for China only
Power
For 1400W Power Supply: 1400W (at 200 to 240 1VAC),
1400W (at 240 VAC) input for China only
For 800W Power Supply: 800W (at 100 to 127 VAC), 800W
(at 200 to 240 1VAC), 800W (at 240 VAC) input for China
only
For 500W Power Supply: 500W (at 100 to 127 VAC), 500W
(at 200 to 240 VAC), 500W (at 240 VAC) input for China only
Temperature
Standard
Operating Support
10° to 35°C (50° to 95°F) at sea level with an altitude derating
of 1.0°C per every 305 m (1.8°F per every 1000 ft) above sea
level to a maximum of 3050 m (10,000 ft), no direct sustained
sunlight.
Maximum rate of change is 20°C/hr (36°F/hr). The
upper limit and rate of change may be limited by the type and
number of options installed.
System performance during
standard operating support may be reduced if operating with a
fan fault or above 30°C (86°F).