• Recommended cable cross-sections
Terminal position Wire function Terminal wire size
rating
Minimum input sire
size
Tightening torque
L1 Phase 4-16mm
1
(12-6AWG) 6mm
1
(10AWG)
105°C (221°F)
10lb in/113 Nm
N (L2) Neutral (phase) 10mm
1
(8AWG) 75°C
(167°F)
Ground
1
Copper wire, solid, or stranded.
Connecting the Input/Output
WARNING: Hewlett Packard Enterprise recommends that this connection is made only by a licensed electrician.
Prerequisites
• Make sure that the upstream protection device is open.
• Make sure that the ground wire is connected.
Installation
23