881627-002 Edition 3
2.3 Display functions
Press the button to activate the menu options. Use the and buttons to scroll through the menu
structure. Press the button to select an option. Press the button to cancel or return to the previous
menu.
Display Function Menu
Main menu Submenu Display information or Menu function
Measurements
Load W VA/Load A pf/Output V Hz/Input V Hz/
Battery V min/Efficiency/Power usage
Control Load Segments Group 1: ON/OFF
Group 2: ON/OFF
These commands override user settings for load segments.
Start battery test Starts a manual battery test
Reset fault state Clears active faults (UPS restart required)
Restore factory settings Returns all settings to original values
Reset power usage Clears power usage measurements
Settings Local settings Sets general parameters
Input/output settings Sets input and output parameters
ON/OFF settings Sets on and off conditions
Battery settings Sets battery configuration
Fault log
Displays event log or alarms
Identification
UPS Type/Part Number/Serial Number/Firmware release/Com card
address
2.4 User settings
The following table displays the options that can be changed by the user.
Description Available settngs Default settings
Local settings
Language [English] [French] [German] [Spanish]
[Italian] [Portuguese] [Russian]
Menus, status, notices and alarms, UPS
fault, event log data and settings are in
all supported languages.
English
User selectable when UPS is
powered the first time.
LCD settings Allows LCD screen brightness and
contrast to be adapted to room light
conditions.
Audible alarm Mode [Enabled] [Disabled on battery] [Always
disabled]
Allows you to enable or disable the
audio alarm if an alarm occurs.
Enabled
Level [High] [Low]
Allows you to set the audio alarm level
if an alarm occurs.
Low
In/Out settings
Output voltage* [100V] [120V] [125V]
On INTL models: [200V] [208V] [220V] [230V]
[240V]
User selectable when UPS is
powered the first time.
*IMPORTANT: The output voltage of the UPS must be set to the same nominal voltage as the facility input
voltage for optimum UPS performance.
Input thresholds [Normal mode] [Extended mode]
Extended mode reduces lower input
voltage to 70V before UPS transfers to
battery.
This can be used if the load can
withstand low voltage supply.
Normal mode
Sensitivity [High] [Low]
High: For sensitive equipment. The UPS
transfers to battery when AC utility
conditions are poor.
Low: For equipment that can withstand
poor utility conditions. The UPS does
not transfer to battery when AC utility
conditions are poor.
High
Load segments - Auto
start delay
[No Delay] [1 s] [2 s]…[65354 s]
The connected equipment is powered
after the specified delay.
Group 1: 3 s
Group 2: 6 s