EasyManua.ls Logo

hpmont HD09 Series - Page 51

hpmont HD09 Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7 Detailed Function Introduction Shenzhen Hpmont Technology Co., Ltd.
-46- HD09 Series User Manual V1.1
Ref. Code Function Description Setting Range [Default]
F17.05 Communication error detection time 0.0 - 1000.0 [0.0s]
When the communication error occurs more than F17.05, reported E0029 failure (SCI communication error),
the inverter continues to run.
F17.05 = 0, the inverter does not detect communication error.
F17.09 Communication write function parameter saving EEPROM choice 00 - 11 [01]
Used to select communication modification parameter, whether it is stored in the EEPROM.
Bits: Except of F00.13, F19.03 function parameter, communication EEPROM storage options
Ten: F00.13, F19.03 function parameter communication EEPROM storage options
0: Not save.
1: Save.
Note:
1. When ten = 1, it may damage the inverter. Please exercise caution.
2. Only when using the communication function parameters, the function code is 0x06 or 0x10 is valid, see Chapter
9 MODBUS communication protocol.
F17.10 Network communication timeout detection time 0.0 - 1000.0 [0.0s]
The frequency converter reports that E0028 is faulty (SCI communication time-out) after the interval
between two received correct data (including local or non-local) continues to exceed F17.10.
F17.10 = 0, do not detecte fault time.

Table of Contents

Related product manuals