Shenzhen Hpmont Technology Co., Ltd. Chapter 10 Parameter
HD09 Series User Manual V1.1 -79-
Ref. Code
Function
Setting Range
Default
Unit
Attribute
Setting
F17: SCI Communication Parameter
F17.00 Data format
0: 1-8-2 format, no parity, RTU
1: 1-8-1 format, even parity, RTU
2: 1-8-1 format, odd parity, RTU
0 1
×
F17.01 Baud rate selection
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
5: 38400bps
3 1
×
F17.02 Local address 0 - 247 2 1
×
F17.03 Host PC response time 0 - 1000ms 1ms 1ms
×
F17.04
Time threshold for
detecting communication
status
0.0 - 1000.0ms
0.0: Not detecting communicaiton over
time
0.0s 0.1s
×
F17.05
Detecting time at
communication error
0.0 - 1000.0ms
0.0: Not detecting communicaiton error
0.0s 0.1s
×
F17.09
Communication write
function parameter of
storage EEPROM method
selection
Units: Communication write function
parameter of storage EEPROM method
selection (Except for F00.13 and F19.03)
Tens: Communication write function
parameter ofstorage EEPROM method
selection for F00.13 and F19.03
0: Without storage EEPROM
1: Storage EEPROM
01 1
×
F17.10
Detecting time when
network communication
over time
0.0 - 600.0s
0.0: Not detecting communicaiton error
0.0s 0.1s
×
F18: Display Control Parameter
F18.00 Language selection
0: Chinese
1: English
0 1
F18.02
Running display parameter
1 setting
0: Reserved
1: Inverter rated current
3: Inverter status
4: Main setting frequency channel
5: Main setting frequency
7: Setting frequency
8 1