What to do if my hpmont HD30-4T011G/015P Inverter is overloaded?
- AAndrew OwensAug 22, 2025
If your hpmont Inverter is overloaded, it could be due to several reasons. The acceleration time might be too short, so you should adjust it using parameters F03.01, F03.03, F03.05, and F03.07. It's also possible that the V/f curve or torque boost settings are causing overcurrent; adjust these using F09.00-F09.06 for the V/f curve and F09.07, F09.08 for torque boost. If a sudden power-off occurred and the motor restarted, set the start mode to speed tracking (F02.00=2). Also, check if the mains supply voltage is too low or if the motor load is too high, and use an inverter with the proper power rating if needed.