EasyManua.ls Logo

HT Neptune - Page 37

Default Icon
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NEPTUNE
EN - 35
Harmonic voltage and current (Autorange)
Harmonic order
Fundamental
frequency
Resolution
Accuracy (*)
(non-zeroed values)
DC
42.5Hz 69Hz
0.1V / 0.1A /0.1%
(5.0rdg+20digits)
1 25 (5.0rdg+10digits)
THD% 0.1%
(10.0rdg+10digits)
Accuracy of harmonic amplitudes expressed in % is evaluated considering the accuracy of parametersratio
(*) Harmonic voltages will be zeroed under the following conditions:
1st harmonic: value <0.5V
DC, 2nd to 25th harmonic: harmonic value <0.5% fundamental value or value <0.5V
(*) Harmonic currents will be zeroed under the following conditions
1st harmonic: value <1%FS[A]
DC, 2nd to 25th harmonic: harmonic value <0.5% fundamental value or value <1%FS[A].
Insulation resistance (M)
Test voltage [V]
Range [M] Resolution [M]
Accuracy
50
0.01 9.99
0.01
(5.0read. + 2digits)
10.0 99.9
0.1
100
0.01 9.99
0.01
(2.0read. + 2digits)
10.0 99.9
0.1
100.0 199.9 (5.0read. + 2digits)
250
0.01 9.99
0.01
(2.0read. + 2digits)
10.0 99.9
0.1
100 499
1
(5.0read. + 2digits)
500
0.01 9.99
0.01
(2.0read. + 2digits)
10.0 199.9
0.1
200 499
1
500 999 (5.0read. + 2digits)
1000
0.01 9.99
0.01
(2.0read. + 2digits)
10.0 199.9
0.1
200 999
1
1000 1999 (5.0read. + 2digits)
Open-circuit voltage: rated test voltage (-0% ÷ 10%)
Short-circuit current: < 6mA (peak) with each rated test voltage
Rated test current: >1mA with 1k x Vnom (50V, 100V, 250V, 1000V), >2.2mA with 230k @ 500V
Input protection: error message for voltage > 10V
Continuity of protective conductors (Lo)
Range [] Resolution []
Accuracy
0.00 9.99
0.01
(2.0%reading + 2digits)
10.0 199.9
0.1
Test current: >200mA DC up to 5 (cables included), resolution 1mA, accuracy (5.0%reading + 5digits).
Open-circuit voltage: 4 < V
0
< 12V
Input protection: error message for voltage > 10V
Phase sequence with 1 terminal (*)
Voltage range L-N, L-PE [V] Frequency range
100.0 999.9
42.5 ÷ 69Hz
(*) Measurement possible by direct contact on the metallic parts of the conductors (not on the insulating sheath)

Table of Contents

Related product manuals