Step 3 After the battery pack is recharged, shut down the UPS. Remove the battery cables
from the battery pack and then from the UPS.
----End
3.4 Recharge Method of the UPS2000-H-6 kVA/10 kVA
3.4.1 Battery Pack Recharge Control Parameters
The following describes how to use the UPS2000-H-10 kVA to recharge a battery
pack.
1. Set charge parameters for the UPS based on the number of battery packs
connected in parallel.
Device
Charge Voltage (V) Charge curr. limit coef.
(C)
UPS2000-H-10 kVA 288±5 0–0.15
ESS-240V12-(9AhBPVBA04, 7AhBPVBA04) Battery
Pack
Quick Guide 3 Transportation and Storage Requirements
Issue 02 (2022-06-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 15