8 SmartLogger Web-based Deployment
Prerequisites
1. The commissioning equipment is available onsite.
2. The system is powered on and alarms are cleared.
3. All devices onsite have been commissioned.
4. Before the deployment, wait until the air conditioner adjusts the temperature
inside the cabinet and the temperature of batteries to the specied
temperature range (5°C to 45°C).
The screenshots in this document correspond to SmartLogger V300R023C00 and are
for reference only.
8.1 Preparations and WebUI Login
Prerequisites
● The operating system of Windows 7 or later is supported.
● Browser: Chrome 52, Firefox 58, or Internet Explorer 9, or a later version is
recommended.
Procedure
Step 1 Connect the network cable between the network port of the PC and the WAN or
LAN port of the SmartLogger.
Step 2 Set the IP address for the PC on the same network segment as the SmartLogger IP
address.
Connected
Port
Item SmartLogger
Default Value
Example PC
Setting
LAN port IP address 192.168.8.10 192.168.8.11
Subnet mask 255.255.255.0 255.255.255.0
LUNA2000-2.0MWH Series Smart String ESS
User Manual 8 SmartLogger Web-based Deployment
Issue 08 (2022-11-15) Copyright © Huawei Technologies Co., Ltd. 157