Item MTS9304A-HD2002
(01074838)
MTS9304A-HD2002
(01074838-001)
Installation mode Installed on a oor
Application
Environment
It can be used in Class C environments and cannot be used
in Class D environments.
● Class C environments refer to sea environments or outdoor land environments (with
simple shielding measures) near pollution sources. If a site is near a pollution source, it
is at most 3.7 km away from salt water, such as the sea and salt lakes, 3 km away from
heavy pollution sources, such as smelteries, coal mines, and thermal power plants, 2 km
away from medium pollution sources, such as chemical, rubber, and galvanization
industries, and 1 km away from light pollution sources, such as packing houses,
tanneries, and boiler rooms.
● Class D environment: It refers to the environment within 500 m away from the ocean.
Figure 2-2 MTS9304A-HD2002 (01074838) interior
(1) Door status sensor
(2) AC power distribution box (3) Power subrack
(4) Ground bar (5) Space for temperature and
humidity sensor
(6) Space for customer
equipment
MTS9300A Telecom Power (Ooredoo, Indonesia,
MTS9304A-HD2002)
User Manual 2 Product Overview
Issue 06 (2021-10-13) Copyright © Huawei Technologies Co., Ltd. 18