C Associations Between UIM Dry Contacts
and Alarms
The DIN/ALM1-3 is a multiplexing port. By default, the DO output function is multiplexed.
Table C-1 Associations between dry contacts and alarms
Port Type
Silk Screen Associated Alarm
Dry contact
input
The default
setting (closed:
alarm; open:
normal) can be
modied.
DIN4 Dry contact input 4
Dry contact
output
The default
setting (closed:
alarm; open:
normal) can be
modied.
DIN1/ALM1 AC Failure, Long AC Failure (disabled by
default)
DIN2/ALM2 LLVD Disconnected
DIN3/ALM3 Rectier Fault (Redundant) (disabled by
default), Rectier Fault (Non-redundant)
(disabled by default), Multi-Rectier Fault,
All Rectiers Fail to Communicate,
Communication Failure, Rectier Fault,
Rectier Protection
ALM4 AC SPD Fault, DC SPD Fault
ALM5 Load Fuse Broken, Battery Fuse Break
MTS9300A Telecom Power (Ooredoo, Indonesia,
MTS9304A-HD2002)
User Manual
C Associations Between UIM Dry Contacts and
Alarms
Issue 06 (2021-10-13) Copyright © Huawei Technologies Co., Ltd. 68