No. Maintenance
Item
Possible Cause Suggestion
2 Check the yellow
indicator status.
Steady on: A minor
alarm or warning is
generated.
Steady on: The SMU is
faulty.
1. Check related components based on
alarms.
2. Replace the SMU.
3 Check the red
indicator status.
Steady on: A critical or
major alarm is
generated.
Steady on: The SMU is
faulty.
1. Check related components based on
alarms.
2. Replace the SMU.
4 Check the LCD
display status.
The LCD cable is loose.
The SMU is faulty.
1. Check that the LCD cable is securely
connected.
2. Replace the SMU.
5 Check that the
SMU can
communicate
with the NMS.
The communications
cable is loose.
Networking parameters
are not correctly set.
1. Check that the communications cable
is securely connected.
2. Check that networking parameters are
correctly set.
4.1.5 Parameters on the SMU
Table 4-5 SMU parameter maintenance
No.
Maintenance Item Possible Fault Cause Suggestion
1 Check whether the
displayed battery capacity
and number of battery
strings are the same as the
actual data.
Parameters are set
incorrectly.
The number of batteries
is changed, or batteries
are replaced.
Set battery parameters
again.
2 Check Charge Current
Limit Coecient. The
value is typically 0.15C10
and adjustable.
N/A Change the value as
required. Otherwise, retain
0.15C10.
3 Check whether the
displayed battery
temperature is the same as
the actual temperature.
The battery temperature
sensor is faulty.
The SMU is faulty.
1. Replace the battery
temperature sensor.
2. Replace the SMU.
MTS9300A Telecom Power (Ooredoo, Indonesia,
MTS9304A-HD2002)
User Manual 4 Maintenance