No.
Check Item
Check Result
1
All cables are connected correctly.
Pass Fail
2
Ground cables are securely connected.
Pass Fail
3
Power cables and ground cables are not coiled and extra parts are
cut off.
Pass Fail
4
The phase sequence is correct.
Pass Fail
5
Power cables and ground cables are routed and bound separately
from other cables.
Pass Fail
6
All circuit breakers are OFF.
Pass Fail
Checking electrical connections
6.2
No.
Check Item
Check
Result
1
All bolts are tightened, especially the bolts used for electric
connection. Flat washers and spring washers are installed properly.
Pass
Fail
2
Cables are bound neatly, and cable ties are secured evenly and
properly in the same direction.
Pass
Fail
3
Cables are routed in a way convenient for maintenance and capacity
expansion.
Pass
Fail
4
There is no unnecessary adhesive tape or cable tie on cables.
Pass
Fail
5
Exposed parts of wires and cable lugs near the wiring terminals are
wrapped by insulation tape or heat shrinking tubing.
Pass
Fail
6
The routing of power cables and monitoring cables meets the
requirements for routing signal cables and power cables and complies
with the cable routing planning.
Pass
Fail
Checking Cable Installation
6.3
1. The power-on commissioning personnel must be at least two qualified electricians. One performs
operations while the other monitors the operations. Irrelevant persons should be warned off.
2. Powering off the PDC disconnects the power supply to the downstream devices. Exercise caution
with this operation when the PDC is supplying power to a working system.
3. If the power indicator on the front panel of the PDC lights up, the PDC is powered on properly.
7
Power-On Commissioning
NOTICE
14
1. Check cable connections and the mechanical performance.
Check that cables are connected correctly outside the cabinet. Check that all bolts are
secured for cables and tighten a bolt if it is loose.
Check that ground cables are properly connected.
(Optional) Switch on and off all circuit breakers and ATSs three times. Ensure that they can