EasyManua.ls Logo

Huawei SmartLi 100Ah - Page 134

Huawei SmartLi 100Ah
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PowerCube 5000
User Manual (SmartLi 100Ah)
9 Parts Replacement
Copyright © Huawei Technologies Co., Ltd.
126
Step 2 Disconnect the power supply.
To replace the AC input SPD: Disconnect the external AC power supply and switch the
SPD circuit breaker to OFF.
To replace the AC output SPD: Turn off the AC output switch of the primary loop and
switch the SPD circuit breaker to OFF.
An AC SPD and its modules can be replaced only when the AC power is off. Otherwise,
personal injury will be caused.
Step 3 Replace the AC SPD.
If...
Then...
A module in the AC SPD is damaged.
Perform Step 3.1.
Both the modules and base of the AC
SPD are damaged.
Perform Step 3.2.
1. Replace a module in the AC SPD, as shown in the following figure.
a. Hold the faulty module by hand and pull it out.
b. Install a new module in the AC SPD.
Figure 9-1 Replacing a surge protection module
2. Replace the AC SPD.
a. Disconnect cables from the faulty AC SPD. Insulate each cable and label it
immediately after disconnecting it.
b. Push the contact plate on the top of the AC SPD upwards using a flat-head
screwdriver and remove the SPD, as shown in the following figure.

Table of Contents