(Optional)
Power cable of
the tracking
system
core outdoor
copper cable with
dual
Conductor cross-
sectional area: 10
mm
2
Note a: The value is valid only if the conductors of the PE cable and AC power cable use the same
material. If the materials are different, ensure that the conductor cross
-sectional area of the PE
cable produces a conductance equivalent to that of the area S/2. The specifications of the PE cable
are subject to this table or calculated according to IEC 60364
b: You are advised to use a soft cable to prevent poor terminal contact due to the bending
Note c: For some models, the outer diameter of a single
core cable ranges from 14 mm to 36 mm
based on the label in the maintenance compartment.
Note d: For some models, when the OT/DT terminal is crimped as shown in the following figure
and the rubber baffle plate of the AC wiring terminal is 112 mm, the maximum conductor cross
sectional area of the single
-core cable can be 400 mm
2
.
Specifications of the Crimped OT/DT Terminal
Specification of the Rubber Baffle Plate