EasyManuals Logo

Huawei SUN2000-40KTL-M3 Quick Guide

Huawei SUN2000-40KTL-M3
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
15
7
System Commissioning
If the solar inverter is connected to the FusionSolar smart PV management system, the
FusionSolar app is recommended. In areas (such as the UK) where the FusionSolar app is not
available, or when a third-party management system is used, only the SUN2000 app can be
used for commissioning.
Access the Huawei app store (http://appstore.huawei.com), search for FusionSolar or
SUN2000, and download the app installation package. You can also scan the QR codes below
to download the apps.
FusionSolar App SUN2000 App
The screenshots are for reference only. The actual screens may vary.
Obtain the initial password for connecting to the solar inverter WLAN from the label on the
side of the solar inverter.
Set the password at the first login. To ensure account security, change the password
periodically and keep the new password in mind. Not changing the password may cause
password disclosure. A password left unchanged for a long period of time may be stolen or
cracked. If a password is lost, devices cannot be accessed. In these cases, the user is liable for
any loss caused to the PV plant.
Set the correct grid code based on the application area and scenario of the solar inverter.

Other manuals for Huawei SUN2000-40KTL-M3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-40KTL-M3 and is the answer not in the manual?

Huawei SUN2000-40KTL-M3 Specifications

General IconGeneral
Max. Efficiency98.7%
European Efficiency98.4%
Max. Input Voltage1100 V
MPPT Operating Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated Output Power40000 W
Rated AC Voltage400 V
Rated AC Frequency50 Hz / 60 Hz
Adjustable Power Factor Range0.8 leading - 0.8 lagging
Total Harmonic Distortion (THD)<3%
DC Reverse-Polarity ProtectionYes
AC Overcurrent ProtectionYes
DC Surge ProtectionType II
AC Surge ProtectionType II
Insulation MonitoringYes
Residual Current MonitoringYes
DC SwitchYes
Protection ClassIP66
Operating Temperature Range-25°C to +60°C
Relative Humidity (Operating)0% - 100%
CoolingNatural Convection
Max. Apparent AC Power44000 VA
AC Voltage Range320 V - 480 V
Operating Altitude4000 m
DisplayLED Indicators
CommunicationRS485, WLAN
Weight43 kg
Max. DC Power60000 W