The rectifiers are hot-swappable, which facilitates installation and maintenance and
lowers the operational expenditure (OPEX).
Robust protection
− A built-in DC surge protective device (SPD) provides 10 kV (8/20 µs) in
differential mode and 20 kV (8/20 µs) in common mode.
− A built-in AC SPD provides 20 kA (8/20 µs) nominal lightning strike discharge
current and 40 kA (8/20 µs) at the maximum.
− Rectifiers provides 5 kA and 6 kV protection.
− The signal ports resist 0.5 kV voltage-to-ground in differential mode and 1 kV in
common mode.
High reliability
− The power system has a service life of 10 years, mean time between failures
(MTBF) of 500,000 hours, and a failure rate of 2000 FITs.