UPS2000-A-(6 kVA-10 kVA) 
User Manual 
 
Copyright © Huawei Technologies Co., Ltd. 
 
Figure 5-38 Shutting down the inverter 
 
 
 
The two methods are called "shutdown operations" in this section. 
Shutting Down a Single UPS in the Parallel System 
Step 1  Perform "shutdown operations" twice for a single UPS in a parallel system within 30s. Then, 
the UPS shuts down and supplies no power. The other UPSs keep working. 
 
The UPSs that have shut down supply no power (the mains indicator, bypass indicator, and battery 
indicator are OFF). If a single UPS in a parallel system shuts down, other UPSs may be overloaded or 
transfer to bypass mode and power supply may be disconnected. 
Step 2  Turn off the AC input and output circuit breakers for the UPS. After all indicators turn off and 
fans stop, the UPS shuts down. 
Step 3  Turn off the external battery circuit breakers (if any), or disconnect battery power cables. The 
UPS exits the parallel system. 
 
To merely shut down the UPS without removing it, skip Step 2 and Step 3. 
----End 
Shutting Down the Inverters of a Parallel System to Transfer to Bypass Mode 
Step 1  Perform "shutdown operations" on each UPS in the parallel system. All inverters shut down at 
the same time, and the parallel system transfers to bypass mode. 
----End 
Shutting Down the Inverters of a Parallel System to Transfer to No Output Mode 
Step 1  Shut down loads.