Step 7  (This step is required only for the UPS with long backup time.) Set the battery capacity to the 
total capacity of all batteries actually connected. The default value is 40 Ah for the 6 kVA 
UPS with long backup time. The default value is 65 Ah for the 10 kVA UPS with long 
backup time, and the value can range from 7 Ah to 999 Ah. 
Figure 5-24 Setting the battery capacity 
 
 
Step 8  (This step is required only for the UPS with long backup time.) Set the charge current limit 
based on actual conditions. The default value is 4.0 A for the UPS with long backup time, and 
the value can range from 1.0 A to 8.0 A with an interval of 0.5 A. 
Figure 5-25 Setting the charge current limit 
 
 
Step 9  Set the parallel mode and the number of redundant UPSs.   
Figure 5-26 Transferring from single mode to parallel mode 
 
 
Step 10  Start each UPS in the parallel system one by one by using either of the following methods for 
the parallel system to work in normal mode: